Preinstallation preparation, Venting installation – FMI VM36E(B User Manual

Page 9

Advertising
background image

www.fmiproducts.com

108796-01UT

9

INSTALLING TRANSITION PIPE AND

STARTER COLLAR

The transition pipe and starter collar shown

in Figure 9 are supplied with fireplace, unat-

tached and ready for installation. Remove

starter collar and set aside. Slide transition

pipe over vent collar and attach with a mini-

mum of three screws. Replace starter collar

over transition pipe and attach using four

screws located on leg stands (five used on

model M42E). To install B-vent piping, slide

first piece of B-vent over transition pipe and

attach with either a minimum of two screws

or other means approved by the vent manu-

facturer.

Figure 9 - Installing Transition Pipe and

Starter Collar

B-Vent Piping

Transition Pipe

Starter Collar

Vent Collar

PreINstallatIoN PreParatIoN

Continued

VeNtING INstallatIoN

at 60° or greater. The total vertical height in

this example represents the minimum height

of 8 feet and therefore the allowable lateral

is 6 feet when the 75% rule applies. If the

lateral length must exceed 75% then the

system must be sized in accordance with the

Category I venting tables.
Example 2: Shows a multiple offset each at

45° of inclination. Multiple offsets are permit-

ted if they do not exceed 45° of inclination. The

total lengths of the two offsets are not required

to meet the 75% allowable rule.
Example 3: Shows a single offset at 45° of

inclination and therefore the lateral length at

10 feet of offset does not have to meet the

75% rule.
In each case the offsets must be supported

and firestops must be positioned wherever

the vent must pass through a sub-floor, ceil-

ing joist or an attic overhang. The vent pipe

must terminate vertically into a listed type vent

cap and extend a sufficient height through

an approved roof flashing, roof jack or a roof

thimble. At all points the listed clearances

must be maintained.
Vent terminations must be located in ac-

cordance with height and proximity rules of

NFPA No. 54. These rules apply to vents at

12" diameter or less and require a minimum

height in accordance with the roof pitch and a

minimum of 8 ft. distance from a vertical wall

or obstruction (see Figure 11, page 10).

A B-type venting system must be connected

to appliance for venting to the outside of

building.
The following section is provided as a guide

to a standard B-type vent installation.
Standing codes requirements concerning B-

type vent installations may vary within your

state, province or local codes jurisdiction.

Therefore, it is recommended that you check

with your local building codes for specific

requirements or in absence of local codes,

follow Section 7.0 of the current National Fuel

Gas Code ANSI Z223.1/NFPA 54.
This gas appliance must be vented to the

outdoors only and may not be terminated into

an attic space or into a chimney flue servicing

a solid-fuel burning appliance.
This appliance may be vented through a

manufactured chimney system or a masonry

chimney using a B-vent adapter or a chim-

ney liner system if all are listed, inspected

and approved by local codes and/or building

authorities.
The examples shown in Figure 10, page 10

are typical of most B-vent installations and

codes practices.
Example 1: Shows the minimum allowable

system height and lateral offset for a 60° or

greater inclination. Code specifies that offsets

at 60° or greater are considered horizontal

and must follow the 75% rule for lateral to

total vertical system height. Codes also al-

low only one offset in the total system when

Advertising
This manual is related to the following products: