Notice, Detail b detail a, Drain tube installation (see figure 12) – Friedrich 920-087-09 (12/10) User Manual

Page 11: Cover plate installation, Drain kit installation

Advertising
background image

11

FRP012

FOAM

GASKET

OVERFLOW

SLOTS

DETAIL B

DETAIL A

COVER

PLATE

FOAM

GASKET

SCREWS

½” O.D. TUBE

MOUNTING

PLATE

NUT

External Drain (for new

construction or unit replacement)

When.using.an.external.drain.system,.the.condensate.is.removed.through.

either.of.two.drain.holes.on.the.back.of.the.wall.sleeve...Select.the.drain.

hole.which.best.meets.your.drainage.situation.and.install.the.drain.kit..

Seal.off.the.other.with.a.cover.plate.

Drain Tube Installation (See Figure 12)

1. Peel.the.backing.tape.off.the.gaskets.and.apply.the.sticky.side.

to.one.cover.plate.and.one.mounting.plate.as.shown.in.Details.

A.and.B.

2. Place.the.drain.tube.through.the.gasket.and.the.mounting.plate.

with.the.flange.toward.the.wall.sleeve.

3. Attach.the.drain.tube.assembly.to.one.of.the.two.drain.holes.at.the.

rear.of.the.wall.sleeve...The.large.flange.on.the.mounting.plate.is.

positioned.at.the.bottom.of.the.sleeve.facing.toward.the.sleeve,.

Detail.B...When.the.drain.tube.is.positioned.at.the.desired.angle,.

tighten.the.screws..

Cover Plate Installation

4. Mount.the.foam.gasket.to.the.cover.plate...Using.two.#10.x.½".sheet.

metal.screws.(provided),.attach.the.cover.plate.to.the.remaining.

drain.hole...Make.certain.the.large.flange.on.the.plate.is.positioned.

at.the.bottom.of.the.sleeve.

5. Discard.the.additional.cover.plate,.gasket,.machine.screws,.and.

locknuts.

NOTE:.

The.large.flange.on.the.mounting.plate.is.positioned.at.the.bottom.of.the.sleeve.facing.toward.the.sleeve...The.drain.tube.must.be.rotated.to.a.

horizontal.position.to.allow.for.the.wall.sleeve.to.be.installed.into.the.wall...Once.the.wall.sleeve.is.installed,.return.the.drain.tube.to.a.downward.

angle.

Figure 12

Drain Kit Installation

NOTICE

If the wall sleeve has not been installed, the drain tube

must be rotated to a horizontal position until after the

sleeve is installed. Tighten the mounting plate screws

when the tube is in the proper position. Make certain that

the four overflow slots at the rear of the wall sleeve are not

blocked (See Figure 12).

When sealing the sleeve on the outside of the building, be

careful NOT to let the sealant block the two condensate

drain holes or the four overflow slots at the bottom flange

of the sleeve.

Potential property damage can occur if instructions are

not followed.

Advertising