Electrical wiring for 265 volt models, Warning, Electrical shock hazard – Friedrich 920-087-09 (12/10) User Manual

Page 14: Power cord installation

Advertising
background image

14

TABLE 2

Model

Heater kW

Power Cord Kit

Voltage

Amperage

Receptacle

PDE07K

0.0

PXPC23000

230/208

15

NEMA.6-15r

PDE/PDH07K

2.0

PXPC23015

230/208

15

NEMA.6-15r

3.0

STD

230/208

20

NEMA.6-20r

PDE09K

0.0

PXPC23000

230/208

15

NEMA.6-15r

PDE/PDH09K

2.0

PXPC23015

230/208

15

NEMA.6-15r

3.0

STD

230/208

20

NEMA.6-20r

5.0

PXPC23030

230/208

30

NEMA.6-30r

PDE12K

0.0

PXPC23000

230/208

15

NEMA.6-15r

PDE/PDH12K

2.0

PXPC23015

230/208

15

NEMA.6-15r

3.0

STD

230/208

20

NEMA.6-20r

5.0

PXPC23030

230/208

30

NEMA.6-30r

PDE15K

0.0

PXPC23000

230/208

15

NEMA.6-15r

PDE/PDH15K

2.0

PXPC23015

230/208

15

NEMA.6-15r

3.0

PXPC23020

230/208

20

NEMA.6-20r

5.0

STD

230/208

30

NEMA.6-30r

PDE/PDH07R

2.0

PXPC26515

265

15

NEMA.6-15r

3.0

STD

265

20

NEMA.6-20r

PDE/PDH09R

2.0

PXPC26515

265

15

NEMA.6-15r

3.0

STD

265

20

NEMA.6-20r

5.0

PXPC26530

265

30

NEMA.6-30r

PDE/PDH12R

2.0

PXPC26515

265

15

NEMA.6-15r

3.0

STD

265

20

NEMA.6-20r

5.0

PXPC26530

265

30

NEMA.6-30r

PDE/PDH15R

2.0

PXPC26515

265

15

NEMA.6-15r

3.0

PXPC26520

265

20

NEMA.6-20r

5.0

STD

265

30

NEMA.6-30r

Electrical Wiring for 265 Volt

Models

NOTE:.

It.is.recommended.that.the.PXSB.subbase.assembly,.the.

PXCJA.conduit.kit.(or.equivalent).be.installed.on.all.hardwire.

units...If.installing.a.flush-floor.mounted.unit,.make.sure.the.

chassis.can.be.removed.from.the.sleeve.for.service.and.

maintenance.

WARNING

Electrical Shock Hazard

Turn off electrical power before service

or installation.

ALL electrical connections and wiring

MUST be installed by a qualified

electrician and conform to the National

Code and all local codes which have

jurisdiction.

Failure to do so can result in property

damage, personal injury and/or death.

Power Cord Installation

All.265V.PTAC/PTHP.units.come.with.a.factory.installed.non-LCDI.

power.cord.for.use.in.a.subbase..If.the.unit.is.to.be.hard-wired.refer.to.

the.instructions.below.

To install the line voltage power leads and conduit

to chassis, follow the instructions below and refer

to Figures 25-27 on page 19. PXCJA Conduit Kit

is required with this setup.

1. Follow. the. removal. process. of. the. chassis’s. junction. box..

(Figure.25,.step.2,.page.19).

2. .Prepare.the.265V.(or.230V).power.cord.for.connection.to.the.chas-

sis’.power.cord.connector.by.cutting.the.cord.to.the.appropriate.

length.(refer.to.Figure.26.and.follow.Figure.15)...Power.cord.harness.

selection.shown.on.Table.2.on.page.14.

Advertising