PTAC Installation Recommendations

PTAC.units.should.be.installed.

no.closer.than.12".apart.when.

two. units. are. side. by. side.. . If.

three.or.more.PTAC.units.are.to.

operate.next.to.one.another.allow.

a.minimum.of.36".between.units...

Also,.a.vertical.clearance.of.60".

should.be.maintained.between.

units. installed.. . In. the. interior.

of.the.room.the.unit.should.be.

located.a.minimum.of.1/4".from.

the.floor.and.a.minimum.of.36".

from.the.ceiling.

For. minor. obstructions.

such.as.lamp.poles.or.small.

shrubbery. a. clearance. of.

12".from.the.outdoor.louver.

should.be.maintained.

For.major.obstructions.such.

as. a. solid. fence,. wall. or.

other.heat.rejecting.device.

like. a. condensing. unit,. a.

minimum. distance. of. 36".

should.be.kept.

For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances

below:

For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:

The.above.suggestions.are.for.reference.only.and.do.not.represent.all.possible.installations...Please.contact.Friedrich.for.information.regarding.affects.of.other.

installation.arrangements...By.following.these.simple.recommendations.you.can.be.confident.that.your.Friedrich.PTAC.will.provide.years.of.worry.free.operation.

Figure 1

Figure 2

FRP002

PTAC

SHRUB

POLE

FENCE OR WALL

C

A

T

P

C

A

T

P

TYPICAL BUILDING ( PLAN VIEW )

CONDENSING UNIT

12"

36"

36"

36"

36" MINIMUM, MAJOR

OBSTRUCTIONS

12" MINIMUM, MINOR

OBSTRUCTIONS

FRP001

THREE OR MORE PTACs

ADJACENT 36" MINIMUM

GROUND FLOOR PTACs

6" MINIMUM FROM GRADE

TWO ADJACENT PTACs

12" MINIMUM

TYPICAL

WINDOW

VIEW: OUTSIDE BUILDING ELEVATION

60" VERTICAL

MINIMUM

BETWEEN

PTACs

12"

6"

36"

60"