Digital control user input configuration, Dip switch, Dip switches – Friedrich 920-087-09 (12/10) User Manual

Page 23: Dip switch setting

Advertising
background image

23

The.adjustable.control.dip.switches.are.located.at.the.lower.left.hand.portion.of.the.digital.Smart.Center..The.inputs.are.only.visible.and.accessible.with.the.

front.cover.removed.from.the.PTAC.

Digital Control User Input Configuration

Switch

Description

Function

Factory Setting

Option

1

Emergency.Heat.Override.

for.PDH.Heat.Pump.

Models

Enables.electric.heat.only.operation.in.the.event.of.a.com-

pressor.failure.on.HP.models.

Down.-.Normal.Operation

Up.-.Overrides.compressor.operation..

(PDH.models.only)

2

Wall.Thermostat.Switch

Enables.the.use.of.a.wall.thermostat.or.unit.controls

Down.-.Unit.Controls

Up.-.Enables.Wall.Thermostat.Usage

3

Fan.Cycle.for.Heating

Allows.selection.of.continuous.fan.or.cycling.in.heating.mode.

Down.-.Cycle

Up.-.Continuous

4

Fan.Cycle.for.Cooling

Allows.selection.of.continuous.fan.or.cycling.in.cooling.mode.

Down.-.Continuous

Up.-.Cycle

5

Setpoint.Switch.1

Allows.the.temperature.setpoint.range.to.be.adjusted.

Down

61F-86F

Up

63F-80F

Down 65F-78F

Up 68F-75F

6

Setpoint.Switch.2

Down

(16C-30C) Down (18C-28C) Up

(19C-26C)

Up (20C-24C)

7

Room.Freeze.Protection

Allows.the.unit.to.ensure.the.indoor.room.temperature.does.
not.fall.below.40F.even.when.turned.off.

Down.-.Freeze.Protection.Enabled

Up.-.Freeze.Protection.Disabled

FRP028

DIP SWITCH

LOCATION OF

DIP SWITCHES

ON UNIT

1

2

3

4

5

6

7

Freeze guard

Setpoint Limit 2

Setpoint Limit 1

Fan CON/CYC for cooling

Fan CON/CYC for heating

Wall Thermostat enable

Electric heat only (for Heat Pumps)

UP

DOWN

High

Med

Low

Fan

Cool

Heat

Fan Spee

d

Mode

Temperature

Power

Figure 31

Dip Switches

1. Emergency Heat Override – Switch 1

In.the.unlikely.event.of.a.compressor.failure.a.heat.pump.unit.may.

be.switched.to.operate.in.only.the.electric.heat.mode.until.repairs.

can.be.made..Moving.Dip.Switch.1.to.‘ON’.

2. Wall Thermostat Switch 2

In.order.to.enable.the.wall.thermostat.move.Dip.Switch.to.'ON'.

3. Fan Cycle Control – Switch 3-4

All.PTACs.are.shipped.from.the.factory.with.Dip.Switch.3-4.in.

the.‘OFF’.position...In.this.position.the.cooling.fan.cycle.will.run.

continuously.providing.air.circulation.during.the.warm.months...

The.heating.fan.cycle.is.set.to.'cycle'.on.and.off...The.fan.may.

be.set.to.'continuous'.mode.by.switching.Dip.Switch.3.to.'ON'.

position.

4. Electronic Temperature Limiting – Switches 5-6

The.digital.control.is.set.from.the.factory.to.allow.a.temperature.

range.between.61°.F.and.86°.F.in.both.heating.and.cooling.

mode..Dip.Switches.5-6.can.be.used.to.set.high.and.low.limits.for.

either.heating.both,.cooling.both.or.both.

From.the.factory.switches.are.in.the.down.'OFF'.position..The.

chart.below.shows.the.available.electronic.limiting.ranges.

5. Room Freeze Protection – Switch 7

Units.are.shipped.from.the.factory.with.the.room.freeze.protection.

enabled...Room.Freeze.Protection.can.be.switched.off.at.the.

owner’s.preference.by.moving.Dip.Switch.7.to.‘OFF’..This.feature.

will.monitor.the.indoor.room.conditions.and.in.the.event.that.the.

room.falls.below.40°F.the.unit.will.cycle.on.high.fan.with.the.

electric.heater..This.occurs.regardless.of.mode.

Dip Switch Setting