IMPORTANT: For natural gas, check gas line

pressure before connecting heater to gas line.

Gas line pressure must be no greater than

10.5" W.C.. If gas line pressure is higher,

heater regulator damage could occur.

CAUTION: For propane/LP

gas, never connect heater di-

rectly to the propane/LP supply.

This heater requires an external

regulator (not supplied). Install

the external regulator between the

heater and propane/LP supply.

For propane/LP gas, the installer must supply

an external regulator. The external regulator will

reduce incoming gas pressure. You must reduce

incoming gas pressure to between 11" and 14"

W.C.. If you do not reduce incoming gas pres-

sure, heater regulator damage could occur. Install

the external regulator with the vent pointing down

as shown in Figure 14. Pointing the vent down

protects it from freezing rain or sleet.

CAUTION: Use only new, black

iron or steel pipe. Internally-tinned

copper tubing may be used in

certain areas. Check your local

codes. Use pipe of large enough

diameter to allow proper gas vol-

ume to heater. If pipe is too small,

undue loss of volume will occur.

Typical Inlet Pipe Diameters

16-18,000 Btu/hr models - 3/8" or greater
26-30,000 Btu/hr models - 1/2" or greater

Installation must include equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up.

NPT tap must be upstream from heater (see

Figure 15, page 12).

Mounting Base Feet to Floor

1. Remove front panel (see Removing Front

Panel of Heater, page 9).

2. Position heater with base feet in desired

location. Mark holes for drilling. Remove

heater with base.

3. For carpeted floors, make a small cut with

a sharp knife at marked locations prior to

drilling. If mounting base to a wood floor,

drill 1/8" diameter hole, 3/4" deep. (Do not

use anchors in wood floors).

If mounting base to a concrete floor, drill with

1/4" diameter concrete drill bit, 13/8" into

floor. Insert anchors completely into holes.

4. Reposition heater with base feet over holes.

Secure base to floor with wood screws. See

Figure 13.

CONNECTING TO GAS SUPPLY

WARNING: This appliance

requires a 3/8" NPT (National

Pipe Thread) inlet connection to

the pressure regulator.

WARNING: A qualified service

person must connect heater to gas

supply. Follow all local codes.

WARNING: For natural gas, never

connect heater to private (non-utility)

gas wells. This gas is commonly

known as wellhead gas.

INSTALLATION

Continued

Propane/LP

Supply Tank

External

Regulator

with Vent

Pointing

Down

Figure 13 - Installing Base Feet (actual

heater may vary from illustration)

Figure 14 - Equipment Regulator with

Vent Pointing Down

3. Align holes in base foot with mounting holes

on bottom of cabinet (see Figure 13).

4. Secure base foot to heater using sheet

metal screws.

5. Repeat for other side.

Sheet

Metal

Screw

Wood

Screw

Base Foot