Air for combustion and ventilation – FMI PFS US VSHRP26M User Manual

Page 6

Advertising
background image

www.fmiproducts.com

125311-01A

6

DETERMINING FRESH-AIR FLOW

FOR HEATER LOCATION

Determining if You Have a Confined or

Unconfined Space

Use this work sheet to determine if you have

a confined or unconfined space.

Space: Includes the room in which you will install

heater plus any adjoining rooms with doorless

passageways or ventilation grills between the

rooms.

1. Determine the volume of the space (length

x width x height).

Length x Width x Height =__________cu. ft.

(volume of space)

Example: Space size 20 ft. (6.1m) (length) x

16 ft. (4.88m) (width) x 8 ft. (2.44 m) (ceiling

height) = 2,560 cu. ft. (72.49 m

2

)(volume of

space)

If additional ventilation to adjoining room

is supplied with grills or openings, add the

volume of these rooms to the total volume

of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example: 2,560 cu. ft. (72.49 m

2

) (volume of

space) x 20 = 51,200 (maximum Btu/Hr the

space can support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free heater

_________ Btu/Hr

Gas water heater* _________ Btu/Hr

Gas furnace

_________ Btu/Hr

Vented gas heater _________ Btu/Hr

Gas heater logs

_________ Btu/Hr

Other gas appliances* + _________ Btu/Hr

Total

= _________ Btu/Hr

* Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the

outdoors and vents to the outdoors.

Example:

Gas water heater

_________ Btu/Hr

Vent-free heater

+ _________ Btu/Hr

Total

= _________ Btu/Hr

4. Compare the maximum Btu/Hr the space

can support with the actual amount of Btu/

Hr used.

_______ Btu/Hr (maximum can support)

_______ Btu/Hr (actual amount used)

Example: 51,200 Btu/Hr (maximum the

space can support)

60,000 Btu/Hr (actual amount of

Btu/Hr used)

AIR FOR COMBUSTION AND VENTILATION

Continued

The space in the example is a confined space

because the actual Btu/Hr used is more than the

maximum Btu/Hr the space can support. You

must provide additional fresh air. Your options

are as follows:
A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an

unconfined space, remove door to adjoining

room or add ventilation grills between rooms.

See Ventilation Air From Inside Building.

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr heater, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support,

the space is

an unconfined space. You will need no additional

fresh air ventilation.

WARNING: If the area in which

the heater may be operated does

not meet the required volume for

indoor combustion air, combus-

tion and ventilation air shall be

provided by one of the methods

described in the National Fuel

Gas Code, ANSI Z223.1/NFPA 54,

the International Fuel Gas Code,

or applicable local codes.

vENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining

unconfined space. When ventilating to an

adjoining unconfined space, you must provide

two permanent openings: one within 12" (30.5

cm) of the ceiling and one within 12" (30.5 cm)

of the floor on the wall connecting the two

spaces (see options 1 and 2, Figure 2, page

7). You can also remove door into adjoining

room (see option 3, Figure 2, page 7). Follow

the National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation

for required size of ventilation grills or ducts.

40,000

60,000

20,000

Advertising