Cleaning and maintenance, Specifications – FMI PFS US VSHRP26M User Manual

Page 18

Advertising
background image

www.fmiproducts.com

125311-01A

18

We also recommend that you keep the burner

tube and pilot assembly clean and free of dust

and dirt. To clean these parts we recommend

using compressed air no greater than 30 PSI.

Your local computer store, hardware store or

home center may carry compressed air in a

can. If using compressed air in a can, please

follow the directions on the can. If you don’t

follow directions on the can, you could dam-

age the pilot assembly.
1. Shut off unit, including pilot. Allow unit to

cool for at least thirty minutes.

2. Inspect burner, pilot and primary air inlet

holes on orifice holder for dust and dirt

(see Figure 30).

3. Blow air through the ports/slots and holes

in the burner.

4. Never inset objects into the pilot tube.
5. Blow air into the primary air holes on the

orifice holder.

Clean pilot assembly also. A yellow tip on the

pilot flame indicates dust and dirt in the pilot

Figure 30 - Pilot Inlet Air Hole

CLEANING AND MAINTENANCE

Continued

Pilot

Assembly

Pilot Air

Inlet Hole

CABINET

Air Passageways

Use pressurized air to clean.
Exterior

Use a soft cloth dampened with a mild soap

and water mixture. Wipe the cabinet to re-

move dust.

SPECIFICATIONS

GWRN18TC, VSHRN18T

• Natural Gas Only

• 18,000 Btu/h

• Pressure Regulator Setting: 6" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 10.5" W.C., Minimum - 7" W.C.

GWRN30TC, VSHRN30T

• Natural Gas Only

• 30,000 Btu/h

• Pressure Regulator Setting: 6" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 10.5" W.C., Minimum - 7" W.C.

GWRN18C, VSHRN18M

• Natural Gas Only

• 6,600/12,000/18,000 Btu/h

• Pressure Regulator Setting: 6" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 10.5" W.C., Minimum - 7" W.C.

GWRN30C, VSHRN30M

• Natural Gas Only

• 6,600/18,000/30,000 Btu/h

• Pressure Regulator Setting: 6" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 10.5" W.C., Minimum - 7" W.C

GWRP16TC, VSHRP16T

• Propane/LP Gas Only

• 16,000 Btu/h

• Pressure Regulator Setting: 8" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 14" W.C., Minimum - 11" W.C.

GWRP26TC, VSHRP26T

• Propane/LP Gas Only

• 26,000 Btu/h

• Pressure Regulator Setting: 8" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 14" W.C., Minimum - 11" W.C.

GWRP16C, VSHRP16M

• Propane/LP Gas Only

• 6,000/11,000/16,000/ Btu/h

• Pressure Regulator Setting: 8" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 14" W.C., Minimum - 11" W.C.

GWRP26C, VSHRP26M

• Propane/LP Gas Only

• 6,000/16,000/26,000 Btu/h

• Pressure Regulator Setting: 8" W.C.

• Inlet Gas Pressure* (in. of water):

Maximum - 14" W.C., Minimum - 11" W.C.

* For purposes of input adjustment.

assembly. There is a small pilot air inlet hole

about 2" from where the pilot flame comes out

of the pilot assembly (see Figure 30). With the

unit off, lightly blow air through the air inlet

hole. You may blow through a drinking straw

if compressed air is not available.