Refrigeration system

Important: All service on refrigeration system must

be performed in accordance with all federal, state and

local laws that pertain to the use of refrigerants. It is

the responsibility of the technician to ensure that these

requirements are met.

CAUTION

• Recharging of unit at other than factory specifications will

void icemaker warranty

Icemaker charge specifications

Model

Charge

Refrigerant

Type

25/50CI400A, 25/50HI400A

20 oz

R404A

25/50CI400W

9 oz

R404A

Refrigerant replacement requirements

1. Non-contaminated refrigerant removed from any

Follett refrigeration system can be recycled and

returned to the same system after completing

repairs. Recycled refrigerant must be stored in a

clean, approved storage container. If additional

refrigerant is required, virgin or reclaimed

refrigerant that meets ARI standard 700-88 must be

used.

2. In the event of system contamination (for example,

a compressor burn out, refrigerant leak, presence
of non-condensibles or moisture), the system must
be repaired, evacuated and recharged using virgin
or reclaimed refrigerant that meets ARI standard
700-88.

3. Follett Corporation does not approve of recovered

refrigerants. Improper refrigeration servicing
procedures will void the factory warranty.

Evacuation

Evacuate the system to a level of 500 microns. When

the 500 micron level is reached, close valves and shut

down the vacuum pump. Allow the system to sit for

approximately 20 minutes. During this period the system

pressure should not rise. If the system pressure rises

and stabilizes there is moisture in the system and further

evacuation is needed. If the pressure continues to rise
check the system for leaks.

Ambients

Air Temperature

1

Minimum

Maximum

Fahrenheit

50 F

100 F

Celsius

10 C

38 C

Water Temperature

2

Minimum

Maximum

Fahrenheit

40 F

90 F

Celsius

4 C

32 C

1 - Ambient air temperature is measured at the air-cooled condenser coil inlet.
2 - Ambient water temperature is measured in the icemaker float reservoir.

Refrigeration data

Ice production

F

C

50
10
60
16
70
21
80
27
90
32

60
16

425
193
410
186
395
180
380
173
365
166

70
21

395
180
380
173
365
166
350
159
335
152

80
27

360
164
345
157
330
150
318
145
305
139

90
32

330
150
315
143
300
137
285
130
273
124

100

38

295
134
285
130
270
123
255

116

243

111

lbs.
kg.
lbs.
kg.
lbs.
kg.
lbs.
kg.
lbs.
kg.

Inlet

W

at

er

Temperatur

e ˚F/˚C

Ambient Air Temperature F/C

Air-cooled icemaker capacity/24 hrs.

Inlet

W

at

er

Temperatur

e ˚F/˚C

F

C

50
10
60
16
70
21
80
27
90
32

60
16

430
195
415
188
401
182
385
175
368
167

70
21

425
193
406
184
386
175
365
166
343
156

80
27

418
190
392
178
365
166
340
154
315
143

90
32

390
177
368
167
345
156
323
147
300
136

100

38

350
159
334
152
318
144
304
138
290
132

lbs.
kg.
lbs.
kg.
lbs.
kg.
lbs.
kg.
lbs.
kg.

Ambient Air Temperature F/C

Water-cooled icemaker capacity/24 hrs.

Ice capacity test

Icemaker production capacity can only be determined by

weighing ice produced in a specific time period.

1. Remove top panel and hopper lid of unit.
2. Weigh and record weight of container used to

catch ice.

3. Run icemaker for at least 15 minutes.
4. Catch ice for 15 or 20 minutes.
5. Weigh harvested ice and record total weight.
6. Subtract weight of container from total weight.
7. Convert fractions of pounds to decimal equivalents

(Ex. 6 lbs 8 oz = 6.5 lbs).

8. Calculate production using following formula:

1440 min. × wt. of ice produced

=

production capacity/

24 hr. period

Total test time in minutes

9. Calculated amount per 24 hours should be checked

against rated capacity for same ambient and water

temperatures in Ice Production Table (above).

Compressor current draw

Air-Cooled Ambient Air Temperature
Fahrenheit

60 F

70 F

80 F

90 F

100 F

Celsius

15.6 C

21.1 C

26.7 C

32.2 C

37.8 C

Locked Rotor Amps

58.8

Gearmotor data

Gearmotor current

2.25A (nominal)

Locked Rotor Amps

14 amps