25CI400A/W • 25HI400A • 50CI400A/W • 50HI400A

33

Problem

Indicators

Corrective Action

Compressor cycles

intermittently.

System status: gearmotor

and fan motor run.

1. Compressor start relay in wrong position.
2. High pressure cutout open due to high head

pressure.

3. Clogged or dirty air filter or condenser coil.
4. Improper ventilation.

5. Defective compressor.

1. Position relay with arrow or word “top”.
2. Check discharge pressure and adjust water regulator

valve.

3. Clean or replace filter, clean condenser coil.
4. Provide inlet and exhaust air provisions per Follett

icemaker installation manual.

5. Replace compressor.

Unit runs but not making ice.

System status: compressor,

gearmotor & fan motor

running.

1. Clogged or dirty air filter or condenser coil.
2. Compressor not pumping.
3. Low refrigerant charge.

1. Clean or replace filter, clean condenser coil.
2. Replace compressor.
3. Check for leaks; repair, evacuate, and weigh in correct

charge.

Compressor and fan motor

will not run.

Gearmotor runs.

1. Compressor switch in OFF position.
2. No output on compressor and fan motor terminals

on control board.

3. Failed fan motor causes high pressure cut-out to

open.

1. Turn compressor switch on.
2. Replace control board.

3. Replace fan motor.

Intermittent noises from

evaporator.

1. Mineral build-up on evaporator surface.

1. Clean evaporator with liquid icemaker cleaner.