INSTAllATION INSTRUCTIONS

SITE REQUIREMENTS

TIMBER FRAMED BUIlDINGS

1.5 It will be necessary to provide additional clearance when

the flue passes through a wall containing any combustible

materials so as to prevent a fire hazard.

1.6 The hole through which the flue will pass, must have a steel

sleeve which is positioned so that an air gap of at least

25mm is maintained between the outer surface of the flue,

and any part of the sleeve.

1.7 For further guidance on the installation of gas appliances in

timber framed buildings, contact your local buildings control

authority.

2. GAS SUPPlY

2.1 Before installation, ensure that the local distribution

conditions (identification of the gas type and pressure) and

the adjustment of the appliance are compatible.

2.2 Ensure that the gas supply is capable of delivering the

required amount of gas, and is in accordance with the rules

in force.

2.3 Factory-sheathed/wrapped soft copper tubing with small

ridges which allow pipe movement are considered to be a

suitable alternative to a pipe sleeve, when recessing the unit

into a cavity wall the gas supply is best fed through the wall

from the outside. Soft soldered joints can only be used

outside the appliance.

2.4 This appliance is supplied complete with a factory fitted

isolation device incorporated into the inlet connection. No

further isolation device is therefore required.

3. vENTIlATION

3.1 This appliance requires no additional ventilation.

4. APPlIANCE lOCATION

NOTE: It is recommended you construct the back panel of the

fireplace from natural materials cut into three or more

sections to prevent cracking. Resin-based materials may

not be suitable. This appliance is an effective heat

producer and attention must be paid to the construction

and finish of the fireplace.

4.1 This appliance must stand on a non combustible hearth that

is at least 12mm thick. If the fire is greater than 50mm

above the floor, then no hearth is required, although due

consideration should be given to how the heat may affect

the floor material.

4

AR0184

A

B

C

D

E

F

DIMENSIONS

MIN

MAX

A

420 mm 450 mm

B

560 mm 575 mm

C

237 mm

-

D

300 mm

-

E

420 mm

-

F

12 mm

-

4.2 The minimum opening dimensions are shown, Diagram 4.

4.3 This appliance can only be installed on an outside wall with

suitable clearances for the flue terminal and guard (if

required).

4.4 This appliance is not suitable for installation into a

combustible wall. All combustible material must be

removed from the area shown, Diagram 5.

5

AR1227

720

420

150

560

300

860

4.5 The maximum depth of combustible shelf is 150mm at a

minimum height of 300mm above the fireplace opening.