Cpg072, Roduct, Pecifications – Goodman Mfg SS-CPG36-72 User Manual

Page 10

Advertising
background image

10

www.goodmanmfg.com

SS-CPG36-72

SS-CPG36-72

www.goodmanmfg.com

11

P

roduct

S

PecificationS

P

roduct

S

PecificationS

P

rodUCt

s

PeCiFiCations

— CPG072

CPG072

1403B***B*

CPG072

1403B***C*

CPG072

1404B***B*

CPG072

1404B***C*

CPG072

1407B***B*

CPG072

1407B***C*

Cooling Capacity
Total BTU/h

71,000

71,000

71,000

71,000

71,000

71,000

Sensible BTU/h

48,280

49,800

48,280

49,800

48,280

49,800

EER / IEER

11.1 / 11.2

11.0 / 11.2

11.1 / 11.2

11.0 / 11.2

11.1 / 11.2

11.0 / 11.2

Decibels

78

78

78

78

78

78

AHRI Number

5104774

5582882

5104774

5582882

5104774

5582882

Heating Capacity
High Input / Output KBTU/h

138 / 110.4

138 / 110.4

138 / 110.4

138 / 110.4

138 / 110.4

138 / 110.4

Low Input/ Output KBTU/h

103 / 83

103 / 83

103 / 83

103 / 83

103 / 83

103 / 83

Steady State Efficiency

80

80

80

80

80

80

Temperature Rise Range (°F)

30-60 / 15-45

30-60 / 15-45

30-60 / 15-45

30-60 / 15-45

30-60 / 15-45

30-60 / 15-45

No. of Burners

6

6

6

6

6

6

Evaporator Motor / Coil
Motor Type

Belt Drive

Belt Drive

Belt Drive

Belt Drive

Belt Drive

Belt Drive

# of Wheels (D x W)

1 (11" x 10")

1 (11" x 10")

1 (11" x 10")

1 (11" x 10")

1 (11" x 10")

1 (11" x 10")

Indoor Nominal CFM

2,350

2,350

2,350

2,350

2,350

2,350

Indoor Motor FLA (Cooling)

5.0

5.0

2.5

2.5

2.3

2.3

Horsepower - RPM

1.5-1,725

1.5-1,725

1.5-1,725

1.5-1,725

1.5-1,725

1.5-1,725

Piston Size (Cooling)

0.094

0.094

0.094

0.094

0.094

0.094

Filter Size (Qty)

(4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"

Drain Size (NPT)

¾"

¾"

¾"

¾"

¾"

¾"

R-410A Refrigerant Charge (oz.)

213.0

146.0

213.0

146.0

213.0

146.0

Evaporator Coil Face Area (ft²)

8.9

8.9

8.9

8.9

8.9

8.9

Rows Deep/ Fins per Inch

4/ 16

4/ 16

4/ 16

4/ 16

4/ 16

4/ 16

Motor Sheave

VL44 X 7/8

VL44 X 7/8

VL44 X 7/8

VL44 X 7/8

VL44 X 7/8

VL44 X 7/8

Blower Sheave

AK59 X 1

AK59 X 1

AK59 X 1

AK59 X 1

AK59 X 1

AK59 X 1

Belt

AX53

AX53

AX53

AX53

AX53

AX53

Condenser Fan / Coil
Quantity of Condenser Fan Motors

1

1

1

1

1

1

Horsepower - RPM

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

Fan Diameter/ # Fan Blades

22/ 4

22/ 4

22/ 4

22/ 4

22/ 4

22/ 4

Outdoor Nominal CFM

4,200

4,200

4,200

4,200

4,200

4,200

Face Area (ft²)

18.7

19

18.7

19

18.7

19

Rows Deep/ Fins per Inch

2/ 20

2/ 27

2/ 20

2/ 27

2/ 20

2/ 27

Compressor
Quantity / Stage/ Type

1/ Single/ Scroll

1/ Single/ Scroll

1/ Single/ Scroll

1/ Single/ Scroll

1/ Single/ Scroll

1/ Single/ Scroll

Compressor RLA / LRA

19/ 123

19/ 123

9.7/ 62

9.7/ 62

7.4/ 50

7.4/ 50

Electrical Data
Voltage/ Phase/ Frequency

208-230/ 3/ 60

208-230/ 3/ 60

460/ 3/ 60

460/ 3/ 60

575/ 3/ 60

575/ 3/ 60

Belt-Driven Standard Max Static

1.0

1.0

1.0

1.0

1.0

1.0

Outdoor Fan FLA

1.90

1.90

1.20

1.20

0.90

0.90

Total Unit Amps

25.9

25.9

13.4

13.4

10.6

10.6

Min. Circuit Ampacity¹

31

31

16

16

12

12

Max. Overcurrent Protection²

45 amps

45 amps

25 amps

25 amps

15 amps

15 amps

Entrance Power Supply

1.125"

1.125"

1.125"

1.125"

1.125"

1.125"

Entrance Control Voltage

½"

½"

½"

½"

½"

½"

Operating/Shipping Weight (lbs)

690/ 715

675/ 700

690/ 715

675/ 700

690/ 715

675/ 700

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

² May use fuses or HACR-type circuit breakers of the same size as noted.

Notes

• Always check the S&R plate for electrical data on the unit being installed.

• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for

208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.