Nomenclature, Omenclature, Roduct – Goodman Mfg SS-CPG36-72 User Manual

Page 2: Pecifications

Advertising
background image

2

www.goodmanmfg.com

SS-CPG36-72

SS-CPG36-72

www.goodmanmfg.com

3

P

roduct

S

PecificationS

P

roduct

S

PecificationS

n

omenClatUre

C

P

G

060

045

3

B

*

*

*

A *

1

2

3

4,5,6

7,8,9

10

11

12

13

14

15 16

Revision Levels

Major & Minor

Brand

Factory-Installed Options

C

Commercial

X

No Options

A

Non-powered convenience outlet

Configuration

B

Powered convenience outlet

P

Packaged Unit

C

Low-ambient kit

D

Return air smoke detector

Application

E

Supply air smoke detector

C

Cooling

F

Non-powered convenience outlet;

G

Gas Heat

Low-ambient kit

H

Heat Pump

G

Non-powered convenience outlet;
Return air smoke detector

Nominal Gross Cooling Capacity

H

Non-powered convenience outlet;

036 3 Tons

102

8½ Tons

Supply air smoke detector

048 4 Tons

120

10 Tons

J

Non-powered convenience outlet;

060 5 Tons

150

12½ tons

Return & Supply air smoke detectors

072 6 Tons

180 & 181 15 Tons

K

Non-powered convenience outlet;

090 7½ Tons

240

20 Tons

Low-ambient kit; Supply air smoke detector

L

Non-powered convenience outlet;

Nominal Heating Capacity

Low-ambient kit

CPG

CPC/CPH (Factory-Installed Electric Heat)

Return & Supply air smoke detectors

045 45,000 BTU/h

XXX No Heat

M

Powered convenience outlet;

090 90,000 BTU/h

010 10 kW

030 30 kW

Low-ambient kit

115 115,000 BTU/h

015 15 kW

031 30 kW

N

Powered convenience outlet;

140 140,000 BTU/h

016 15 kW

045 45 kW

Return air smoke detector

210 210,000 BTU/h

018 18 kW

046 45 kW

O

Powered convenience outlet;

350 350,000 BTU/h

020 20 kW

060 60 kW

Return & Supply air smoke detectors

400 400,000 BTU/h

025 25 kW

P

Powered convenience outlet;

See product specifications for heat size(s) available for each capacity.

Supply air smoke detector

Q

Powered convenience outlet; Low-

Voltage

ambient kit; Return air smoke detector

1

208-230/1/60

4 460/3/60

R

Powered convenience outlet; Low-

3

208-230/3/60

7 575/3/60

ambient kit; Supply air smoke detector

T

Powered convenience outlet;

Supply Fan/Drive Type/Motor

Low-ambient kit; Return & Supply

B

Belt Drive

air smoke detectors

D

Direct Drive

U

Non-powered convenience outlet;
Low-ambient kit; Return air smoke detector

Factory-Installed Options

V

Low-ambient kit; Return air smoke detector

X

No Options

W

Low-ambient kit; Supply air smoke detector

A

Downflow Economizer

Y

Low-ambient kit; Return & Supply

H

Disconnect Switch (non-fused)

air smoke detectors

J

Downflow Economizer; Disconnect Switch (non-fused)

Z

Return & Supply air smoke detectors

Note: Not all options available for all products.

Factory-Installed Options

X

Standard Aluminized Heat Exchanger

S

Stainless-Steel Heat Exchanger

Factory-Installed Options


Economizers (Downflow): Based on air conditions, can provide outside air to cool the space.

Electric Heat Kits (CPC and CPH units only): Available in all voltage options.

Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs power to the outlet.

Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit; for use when unit is not running.
When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V
units, increase by 3.75A for 460V units, and increase by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.

Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.

with the disconnect switch (non-fused) when it is ordered.  Please note that for models with a powered convenience outlet option and a disconnect switch
(non-fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-fused) is in the off position.

ambient temperature to 35°F outside air temperature. On 7½- to 20-ton units, cooling operation is extended from 35°F ambient temperature

that for air conditioning (CPC units) and heat pump models (CPH units), the appropriate electric heat kit must be ordered to be factory-installed along

Stainless-Steel Heat Exchanger (CPG units only): A tubular heat exchanger made of 409-type stainless steel is installed in the unit.
Low-Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3- to 6-ton units, cooling operation is extended from 60°F

to 0°F outside air temperature.

Disconnect Switch (non-fused): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the unit.  Please note