Cpg048, Irflow – Goodman Mfg SS-CPG36-72 User Manual

Page 25

Advertising
background image

24

www.goodmanmfg.com

SS-CPG36-72

SS-CPG36-72

www.goodmanmfg.com

25

P

roduct

S

PecificationS

P

roduct

S

PecificationS

a

irFlow

d

ata

— CPG048

s

tandard

d

ireCt

d

rive

— h

orizontal

s

tandard

d

ireCt

d

rive

— d

own

s

hot

CFM

Static

Amps Watts RPM

Speed

Tap

CFM

Static

Amps Watts RPM

Speed

Tap

1592

0.1

2.54

543

815

Low

1612

0.1

2.60

554

789

Low

1528

0.2

2.43

521

858

1548

0.2

2.49

532

832

1464

0.3

2.32

499

901

1484

0.3

2.38

510

875

1380

0.4

2.21

475

930

1400

0.4

2.27

486

904

1296

0.5

2.10

451

959

1316

0.5

2.16

462

933

1828

0.1

3.08

665

892

Med

1846

0.1

3.14

676

866

Med

1700

0.2

2.75

601

924

1718

0.2

2.81

612

898

1606

0.3

2.61

563

966

1624

0.3

2.67

574

940

1531

0.4

2.48

537

990

1549

0.4

2.54

548

964

1401

0.5

2.32

503

1023

1419

0.5

2.38

514

997

1287

0.6

2.22

477

1045

1305

0.6

2.28

488

1019

1123

0.7

2.05

441

1073

1141

0.7

2.11

452

1047

1926

0.1

3.34

740

937

High

1954

0.1

3.43

758

924

High

1825

0.2

3.18

700

965

1853

0.2

3.27

718

952

1712

0.3

3.03

660

989

1740

0.3

3.12

678

976

1598

0.4

2.87

626

1015

1626

0.4

2.96

644

1002

1482

0.5

2.76

596

1032

1510

0.5

2.85

614

1019

1357

0.6

2.62

564

1049

1385

0.6

2.71

582

1036

Note: Assumes dry coil with filter in place; SCFM correction for wet coil = 4%