6

www.goodmanmfg.com

SS-CPG36-72

SS-CPG36-72

www.goodmanmfg.com

7

P

roduct

S

PecificationS

P

roduct

S

PecificationS

P

rodUCt

s

PeCiFiCations

— CPG048 (

Cont

.)

CPG048

1151D***B*

CPG048

1153D***B*

CPG048

1153B***B*

CPG048

1154B***B*

CPG048

1157B***B*

Cooling Capacity
Total BTU/h

45,500

45,500

45,500

45,500

45,500

Sensible BTU/h

35,000

35,000

35,000

35,000

35,000

SEER / EER

13.0 / 11.3

13.0 / 11.3

13.0 / 11.3

13.0 / 11.3

13.0 / 11.3

Decibels

78

78

78

78

78

AHRI Reference #s

4385062

4385063

4385063

4385064

4397608

Heating Capacity
High Input /Output kBTU/h

115 / 92

115 / 92

115 / 92

115 / 92

115 / 92

Low Input /Output kBTU/h

86.25 / 69

86.25 / 69

86.25 / 69

86.25 / 69

86.25 / 69

Steady State Efficiency (AFUE)

80

80

80

80

80

Temperature Rise Range (°F) Hi / Low

40-70 / 25-55

40-70 / 25-55

40-70 / 25-55

40-70 / 25-55

40-70 / 25-55

No. of Burners

5

5

5

5

5

Evaporator Motor / Coil
Motor Type

Direct Drive

Direct Drive

Belt Drive

Belt Drive

Belt Drive

Indoor Nominal CFM

1,600

1,600

1,600

1,600

1,600

Motor Speed Tap (Cooling)

Medium

Medium

--

--

--

Indoor Motor FLA (Cooling)

2.87

2.87

3.8

1.9

2.3

Horsepower - RPM

½ - 1,000

½ - 1,000

1.0 / 1,725

1.0 / 1,725

1½ / 1,725

Piston Size (Cooling)

0.076

0.076

0.076

0.076

0.076

Filter Size (#)

14 x 20 x 2 (4)

14 x 20 x 2 (4)

14 x 20 x 2 (4)

14 x 20 x 2 (4)

14 x 20 x 2 (4)

Drain Size (NPT)

¾”

¾”

¾”

¾”

¾”

R-410A Refrigerant Charge Cir #1(oz.)

103

103

103

103

105

Evaporator Coil Face Area (ft²)

7.0

7.0

7.0

7.0

7.0

Rows Deep / Fins per Inch

4 / 16

4 / 16

4 / 16

4 / 16

4 / 16

Belt Drive Evap Fan Data
# of Wheels (D” x W”)

---

---

(1) 11 x 10

(1) 11 x 10

(1) 11 x 10

Motor Sheave / Blower Sheave

---

---

VL44 X ⅝ / AK66 X 1

VL44 X ⅝ / AK66 X 1

VL44 X ⅝ / AK66 X 1

Belt

---

---

AX52

AX52

AX52

Condenser Fan / Coil
Quantity of Condenser Fan Motors

1

1

1

1

1

Horsepower - RPM

¼ - 1,090

¼ - 1,090

¼ - 1,090

¼ - 890

¼ - 1,075

Fan Diameter / # Fan Blades

22 / 4

22 / 4

22 / 4

22 / 4

22 / 4

Outdoor Nominal CFM

3,800

3,800

3,800

3,800

3,800

Face Area (ft²)

17.0

17.0

17.0

17.0

17.0

Rows Deep/ Fins per Inch

1 / 24

1 / 24

1 / 24

1 / 24

1 / 24

Compressor
Quantity / Stage

1 / Single

1 / Single

1 / Single

1 / Single

1 / Single

Type

Scroll

Scroll

Scroll

Scroll

Scroll

Compressor RLA / LRA

19.9 / 109

13.1 / 83.1

13.1 / 83.1

6.1 / 41

4.4 / 33

Electrical Data
Voltage-Phase-Frequency

208/230-1-60

208/230-3-60

208/230-3-60

460-3-60

575-3-60

Outdoor Fan FLA

1.40

1.40

1.40

0.80

0.60

Total Unit Amps

24.1

17.4

18.3

8.8

7.3

Min. Circuit Ampacity¹

29

21

22

10

8

Max. Overcurrent Protection (amps)²

45

30

30

15

15

Power Supply Conduit Hole

1.125

1.125

1.125

1.125

1.125

Low-Voltage Conduit Hole

½”

½”

½”

½”

½”

Operating Weight/Shipping (lbs)

580/ 605

580/ 605

580/ 605

580/ 605

580/ 605

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

² May use fuses or HACR-type circuit breakers of the same size as noted.

Notes

• Always check the S&R plate for electrical data on the unit being installed.

• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for

208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.