Kitchen Hoods • Type I and Type II

High Velocity Cartridge Filters - Rotating Vane
Method

A. Exhaust

With all the filters in place, determine the total hood
exhaust volume with a rotating vane anemometer as
follows:

1. All cooking equipment should be on. If the hood has

internal short circuit make-up air, it should be turned off.

2. Measure velocities.

Velocity measurements should be taken at three
locations per filter. These must be over the inlet
opening as shown in Fig. 10.

Measure the velocity of each location. A digital
2.75 in. (69.85 mm) rotating vane anemometer
or its equivalent is suggested. The center of the
anemometer should be held 2 in. (50.8 mm) from
the face of the filters as in Fig. 11. It is helpful to
make brackets to keep the anemometer at the 2 in.
(50.8 mm) distance and parallel to the filter. Both
squareness and distance are important for accuracy.

3. Calculate the average slot velocity.

4. Calculate the CFM per linear foot by dividing

the average velocity by a conversion factor
listed in the following table.

5. Calculate each filter’s volumetric flow rate in

CFM by multiplying the average velocity for
each filter by the conversion factor.

1/4 Width

1/4 Width

1/2 Width

1/2 Height

Inlet

Height

Filter

Height

Fig. 10

Cartridge Filter Size

Imperial

Conversion

Factor

Metric

Conversion

Factor

16 in. (400 mm) high with 4 in. (100 mm) high inlet

1.63 1/

ft

3

5.35 1/

m

3

20 in. (500 mm) high with 4 in. (100 mm) high inlet

2.15 1/

ft

3

7.05 1/

m

3

16 in. (400 mm) high with 7 in. (120 mm) high inlet

1.24 1/

ft

3

4.07 1/

m

3

20 in. (500 mm) high with 7 in. (120 mm) high inlet

1.58 1/

ft

3

5.18 1/

m

3

Rotation Vane
Anemometer

2 in.

(50.8 mm)

Fig. 11

Hood exhaust volume =

CFM/linear foot (m

3

/hr / m)

x

Hood Length

(Imperial)

=

206.6

x

9 ft.

=

1859.4 cfm

(Metric)

=

1152

x

2.74 m

=

3156 m

3

/hr

Example:

Measure the slot velocities in ft/min. for a 9 ft. (2.74 m) hood with four 20 x 20 in. (500 x 500 mm) filters with the
standard 4 in. (101.6 mm) opening, three readings per filter.

Average Velocity

=

Sum of Velocity Readings

Number of Readings

(Imperial)

=

5330

12

= 444.2 ft/min.

(Metric)

=

97474

12

= 8123 m/hr

CFM per linear foot

=

Average Slot Velocity

Conversion Factor

(Imperial)

=

444.2 ft/min.

2.15

= 206.6 cfm/linear ft.

(Metric)

=

8123 m/hr

7.05

= 1152 m

3

/hr

Filter Readings (ft/min.)

470

440

425

482

430

453

455

431

441

399

439

465

Filter Readings (m/hr)

8595

8047

7772

8815

7864

8284

8321

7882

8065

7297

8028

8504

®