Amerex wiring plan view, Basic wiring diagram – Greenheck Fan Canopy Type Kitchen Hoods 452413 User Manual

Page 21

Advertising
background image

21

Kitchen Hoods • Type I and Type II

POWER SOURCE

MANUAL RESET RELAY

MICROSWITCH

MICROSWITCH

ELECTRIC GAS VALVE

INSTALLER PROVIDED JUNCTION BOXES

PRM

BASIC WIRING DIAGRAM

RED (COMMON)

POWER SOURCE

MANUAL RESET RELAY

YELLOW (N.O)

BLACK (N.C.)

GAS VALVE

MICROSWITCH

BASIC WIRING DIAGRAM

RED (COMMON)

MANUAL RESET RELAY

YELLOW (N.O)

BLACK (N.C.)

GAS VALVE

SEE NOTE 3

NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL
INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR
EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.

L1

L2

PUSHBUTTON SWITCH

120V/60HZ

K1

Ka

K1b

CURRENT DRAW MAX:
8A RESISTIVE
8A INDUCTIVE
120VAC

NOTES:
1.

DENOTES FIELD INSTALLATION

2.

DENOTES FACTORY INSTALLATION

3. GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF
APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871,
12872, 12873, 12874, 12875 and 12876.
4. K1a and K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.

Amerex Wiring Plan View

®

Advertising