Kitchen Hoods • Type I and Type II

Option A

Relay Part No. 14702

* K1a and K1b are N.O. when K1 is de-energized

Manual Reset Relay
Part No. 14702

K1*

N.O. K1a

K1b N.O.

Push Button

Switch

Gas Valve
See Note 3

1

2

3

5

6

7

8

L1

110V/60HZ

Black

Red

Brown

L2

Snap-Action Switch
Part No. 423878

Option B

Relay Part No. 426151

Ansul Snap-Action Switch
(Switch contacts shown with Ansul
Automan in the cocked position)

Snap-Action Switch
Part No. 423878

Black

Red

Brown

L2 Neutral
L1 Hot

110 VAC/60HZ

5

4

3

2

1

GND

Screw

Power
Indicator

Reset

A

B

Relay Coil

Manual Reset Relay
(Part No. 426151)

Electrical Rating
1/3 HP, 10 AMP, 120 VAC
1/2 HP, 10 AMP, 240 VAC
13 AMP, 28 VDC

Gas Valve
See Note 3

6
9

3
4
7
1

2 Snap-Action Switches provided by manufacturer

may be wired as shown.

Four typical examples shown

Power to cooking
equipment

Shunt Trip Breaker

120 VAC

N

Input

NO

NC

Electric gas valve - If reset relay is
used, see option A or B at right.
Mechanical gas shut off valve does not
require electrical connection.

NO

NC

NO

Input

NC

Voltage Free
Contacts for
Building Alarm(s)

Power to
Fan(s)

Fan
Starter

Terminal strip in
Waterwash Control Panel

NO

NC

3

4

5

6

NO

NC

120 VAC

N

Input

Power to
fan(s)

Fan Starter

Manual Switch

If prohibited by local codes, do not shut down
exhaust fans with this method of wiring.

Note:
1.

Denotes field installation.

2.

Denotes factory installation.

3. Gas Valves: “UL Listed electrically-operated safety valve for natural or LP gas

as needed of appropriate pressure and temperature rating, 110V/60HZ”

or Ansul gas valves.

4. Do not use black wire on snap-action switch in normal installation. Black

wire may only be used for extraneous alarm, light circuits, etc.

Equipment

Alarms

Waterwash

Fans

Amerex Wiring Plan View

®