High velocity cartridge filters - shortridge meter, Example – Greenheck Fan Canopy Type Kitchen Hoods 452413 User Manual

Page 17

Advertising
background image

17

Kitchen Hoods • Type I and Type II

High Velocity Cartridge Filters - Shortridge Meter

A. Exhaust

With all the filters in place, determine the total hood
exhaust volume with a Shortridge meter as follows:

1. All cooking equipment should be on. If the hood has

internal short circuit make-up air, it should be turned
off.

2. Measure velocities

Set up the Shortridge meter. Leave all holes of
VelGrid open. Do NOT tape over holes that are not
over openings. The conversion factor takes this into
account.

Position the grid over each filter. Refer to Fig. 12

• Take velocity readings for each filter.

3. Calculate each filter’s volumetric flow rate as follows:

Calculate each filter’s average velocity by summing
the velocity readings and dividing by the number of
readings for each filter.

Multiply the average velocity by the conversion factor
to obtain the volumetric flow rate for each filter.

4. Calculate the hood’s total volumetric flow rate by

summing the volumetric flow rate of each individual
filter in the hood as calculated in Step 3.

1/2 width

1/2 height

Fig. 12

Nominal Filter Size

(H x L)

Imperial

Conversion

Factor

Metric

Conversion

Factor

Inches

Millimeters

16 x 16

400 x 400

1.22

ft

2

.113

m

2

16 x 20

400 x 500

1.67

ft

2

.155

m

2

20 x 16

500 x 400

1.21

ft

2

.112

m

2

20 x 20

500 x 500

1.50

ft

2

.139

m

2

NOTE

For best accuracy multiply the velocity of each filter
by its conversion factor and sum the flow rates.
Averaging the velocity measured for all filters may
cause error.

Example:

Measured velocities for 20 x 20 filter = 282 ft/min. (5157 m/hr)

Flow rate for one filter =

Conversion

Factor

x

Average

Velocity

(Imperial)

=

1.50

x

282 ft/min.

=

423.0 cfm

(Metric)

=

.139

x

5157 m/hr

=

717 m

3

/hr

Total hood flow rate

= (Filter 1 Flow Rate) +

+ (Filter X Flow Rate)

(Imperial)

= 423.0 + 421.8 + 420.7 + 418.2 =

1683.7 cfm

(Metric)

= 717 + 717 + 715 + 711

=

2860 m

3

/hr

Edge of outlet/inlet
active face area

Maintain 1½ inch
(38.1 mm) margin

Maintain 1½ inch
(38.1 mm) margin

Place standoff spacers against
face of outlet or inlet grill,
filter, coil, etc.

Tubing harness

Neckstrap

External read jack

Extension rods

Swivel bracket

Tubing connectors

Pushbutton handle and plug

Handle bracket

Captive knob screws

Pressure input ports

®

Advertising