Configuration cable, Configuration cable –3 – GE P485 User Manual

Page 13

Advertising
background image

INSTALLATION

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

2–3

CONFIGURATION CABLE

The PC connector is indicated as B in Figure 2-1: P485 electrical connections on page 2–2.
This connector is used to connect the P485 to a PC using the configuration cable for
configuration and monitoring purposes.

A P485/D485 configuration cable can be purchased from GE Multilin. The wiring for the
configuration cable is shown below.

Figure 2-3: Configuration cable

The pinout for the modular 4/4 RJ11 connector (connects to the P485) is shown below.

Figure 2-4: Configuration cable (P485 end)

The pinout for the DSUB 9-pin serial plug (connects to the PC) is shown below.

Table 2–2: Configuration cable pin assignments (P485 end)

Pin

Description

1

Signal ground

2

Signal ground

3

RS232 Rx, data input to P485

4

RS232 Tx, data output from P485

Table 2–3: Configuration cable pin assignments (PC end)

Pin

Description

1

Not connected

2

RS232 Rx, data input to PC

3

RS232 Tx, data output from PC

4

Not connected

5

Ground

6 to 9

Not connected

1

2

3

4

5

6

7

8

9

1

2

3

4

D-sub 9 female (PC)

Modular 4/4 RJ11 connector (P485)

Ground

Ground

Rx

Tx

RS232 Tx

RS232 Rx

Ground

Connects to PC serial port

Connects to P485

1

2

3

4

Advertising