P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

INSTALLATION

CONFIGURATION

SWITCHES

The configuration switches are used to set the Profibus node address. Normally, these
switches are covered by a plastic hatch. Note that the node address can not be changed
during runtime, i.e. the P485 requires a reset for any changes to have effect. Recycle the
power supply to reset the module

Figure 2-10: P485 configuration switches

The node address is configured using two rotary switches as follows:

Profibus node address = (Switch B

× 10) + (Switch A × 1)

Table 2–5: P485 status indicators

Number

Description

State

Status

1

Profibus online

Off

Not online

Green

Online

2

Profibus offline

Off

Not offline

Red

Offline

3

Not used

-

-

4

Profibus
diagnostics

Off

No diagnostics present

Red, flashing 1 Hz

Error in configuration

Red, flashing 2 Hz

Error in user parameter data

Red, flashing 4 Hz

Error in initialisation

5

Subnet status *
(Modbus)

Off

Power off

Green, flashing

Initializing and not running

Green

Running

Red

Stopped or subnet error, or timeout

6

Device status

Off

Power off

Alternating Red/
Green

Invalid or missing configuration

Green

Initializing

Green, flashing

Running

Red, flashing

If the device status LED is flashing in a
sequence starting with one or more red
flashes, note the sequence pattern and
contact GE Multilin

*

This LED turns green when all transactions have been active at least once. This includes any
transactions using “change of state” or “change of state on trigger”. If a timeout occurs on a
transaction, this LED will turn red.