FRAME AND COMMAND EDITORS

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

6–3

SPECIFYING A NEW

COMMAND

Select ‘Add Command’ as described earlier.

This example is taken from a Modbus RTU implementation, which means that the frame
will always consist of one byte for slave address, one byte for function code and two bytes
for CRC. Furthermore, each command always consists of a query and a response.

The Modbus RTU specific frame objects are already in place and a data object is inserted
between the function code and the CRC. These objects cannot be moved or deleted,
however it is possible to add objects between the function code and the CRC.

Figure 6-4: Specifying a new command

First, enter a name for the command in the Command Name field (A) and an identifier in
the Command ID field (B). If the command is allowed to be broadcast on the sub-network,
check the Allow Broadcasting check box (C).

The Query (D) field has the following characteristics:

Query

Column

1: Slave Address.

2: Modbus Function Code

3: See below

4: Error Check field.

DisplayName

Slave Address

Function

Data

Checksum

Protocol specific; cannot be altered.

(See below)

Object Type

Byte

Byte

Data

Checksum

Modbus defines this object as a byte.

(See below)

Value

[SlaveAddress]

ID

User

User

Linked to the actual ‘Slave

Address’ parameter in the

parameter window.

This value is linked to the

Command ID field.

(See below)

Linked to “User”.

Determined by user at

configuration by selecting

the Error Check object in

the parameter window.