APPLICATION EXAMPLE

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

9–7

STEP 2: SELECTING THE

SUB-NETWORK

PROPERTIES

The second step in the configuration wizard is to select the sub-network properties.

1.

Set the Modbus network properties as follows: baud rate to 19200, with 8 data bits, no
parity, RS485 physical standard, and 1 stop bit.

Figure 9-6: Modbus network properties

2.

Click Next to proceed to step 3 of the configuration wizard.

STEP 3: INCLUDE DEVICE

TYPES

The third step in the configuration wizard is to include device types. The PQMII and MM2
devices are added in this step.

1.

The configuration wizard gives the option to create a configuration for a new device or
to load a configuration of saved device.

Figure 9-7: Device types

2.

Configuration files for MM2 and PQMII are supplied with the Enervista P485/D485
Setup software. Click the Load Device button to see the available configuration files.

Figure 9-8: Available Modbus devices