2–4

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

INSTALLATION

Figure 2-5: Configuration cable (PC end)

MODBUS CONNECTOR

The Modbus connector is indicated as C in Figure 2-1: P485 electrical connections on page
2–2. This connector is used
to connect the P485 to the serial network. Based on the
configuration selected in the EnerVista P485/D485 Setup software, the corresponding
signals are activated.

Figure 2-6: Modbus connector

POWER CONNECTOR

The power connector is indicated as D in Figure 2-1: P485 electrical connections on page
2–2. Use this
connector to apply power to the P485.

Pin 1: +24 V DC;
Pin 2: ground

Use 60/75 or 75°C copper (CU) wire only. The terminal tightening torque must be between
5 to 7 lbs-in (0.5 to 0.8 nm).

Figure 2-7: Power connector

5

1

6

9

(female)

Table 2–4: Modbus connector pin assignments

Pin

Description

RS232

RS422

RS485

1

+5 V output (50 mA max)

2

RS232 Rx

3

3

RS232 Tx

3

4

Not connected

5

Ground

3

3

3

6

RS422 Rx +

3

7

RS422 Rx –

3

8

RS485 + / RS422 Tx+

3

3

9

RS485 – / RS422 Tx–

3

3

5

1

6

9