P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

DATA EXCHANGE

Figure 3-2: Data exchange overview

Memory Map

MEMORY LOCATIONS

When configuring the sub-network, use the memory locations shown below:

The PLC exchanges data
via the Profibus network
between its internal input
area and the input area
of the P485

Profibus network

The PLC exchanges data
via the Profibus network
between its internal output
area and the output area
of the P485

The data in the input area of
the P485 contains data received
from nodes on the Modbus
sub-network (sent in to the P485
from the sub-network)

The data in the output area of
the P485 contains data received
from Profibus. In this case, it is
the CT PRIMARY setting of the
PQMII meter.

0x0000

0x0200

0x0400

Input data area

Output data area

General data area

Modbus sub-network

Current Ia

CT PRIMARY

Internal memory buffer

of the P485

PLC memory

I/O inputs

I/O outputs

Current Ia

CT PRIMARY

Modbus slave (e.g. PQMII)

CT PRIMARY setting

Current Ia actual value

Address

Contents

Access

0x0000 to 0x0001

Status register

read/write

0x0002 to 0x00F3

Input data area

read/write

0x00F4 to 0x01FF

Reserved

-

0x0200 to 0x0201

Control register

read only

0x0202 to 0x02F3

Output data area

read only

0x02F4 to 0x03FF

Reserved

-

0x0400 to 0x7FF

General data area

read/write