DIAGNOSTIC STATUS CODES

TRANSISTOR PUMP CONTROL

Page 48

January 2000

PUMP

STATUS CODE

DESCRIPTION OF

STATUS

CAUSE OF STATUS INDICATION

-142

Pump Controller “motor current
sensor” input is missing.

This status code is displayed when the voltage at the
current sensor is greater than 0.1 volts with no current
flowing in the motor circuit.

MEMORY RECALL

NO

CORRECTIVE ACTIONS

TROUBLE-SHOOTING DIAGRAM

Circuits valid

for

Pump

Controller



SYMPTOM
No power to pump motor in
control range.

POSSIBLE CAUSE
Control is defective.

=Replace controller unit.


POWER

CONNECTIONS

POS

A1

NEG

A2

FI

EL

D

ARMATURE

+

-

FU1

FU3

KEY SWITCH

P1

P2

P3

P12

LINE

FU6

P19

P21

TO

TRACTION

CARD

SPEED L

IMI

T 1

SPEED L

IMI

T 2

SPEED L

IMI

T 3

TO TRACTION

P10 - BDI

PY7

PY12
PY10
PY11

PUMP

STATUS CODE

DESCRIPTION OF STATUS

CAUSE OF STATUS INDICATION

-143

Pump Controller “motor current
sensor” input is too low.

This status code is displayed when the voltage at the
current sensor is greater than 0.1 volts with no current
flowing in the motor circuit.

MEMORY RECALL

NO

CORRECTIVE ACTIONS

TROUBLE-SHOOTING DIAGRAM

Circuits valid

for

Pump

Controller


SYMPTOM
No power to pump motor in
control range.

POSSIBLE CAUSE
Control is defective.

=Replace controller unit.


POWER

CONNECTIONS

POS

A1

NEG

A2

FI

EL

D

ARMATURE

+

-

FU1

FU3

KEY SWITCH

P1

P2

P3

P12

LINE

FU6

P19

P21

TO

TRACTION

CARD

SPEED L

IMI

T 1

SPEED L

IMI

T 2

SPEED L

IMI

T 3

TO TRACTION

P10 - BDI

PY7

PY12
PY10
PY11