ADJUSTABLE FEATURES

SX TRANSISTOR CONTROLS

Page

58

January 2000

FUNCTION 6

FW RATIO

(Push

6)

This function sets the ratio between armature and field

current when operating below the Field Weakening Start

point. The setting represents the quantity of field current

changed for each 1 amp of armature current changed.


Max Fld Ref

Set

Resolution Per Unit Value

40

0 to 10

0.029 amps


The ratio value (VAL) is the set value divided by 10 and

rounded to the whole number.

Example: Setting of 45 = 45/10 = 4.5 = 4 VAL

I

FIELD

= VAL (I

MOTOR

x 0.029)


FUNCTION 7

MIN FIELD CURRENT

( Push 7 )

This function allows the adjustment of the field weakening

level in order to set the top speed of the motor.

Min Max Set

Resolution Per Unit Value

0

40

51 to 255 0.185

MIN I

F

= (VAL-51) X 0.185

Important Note: This function is used to optimize motor
and control performance, and this setting will be
determined by GE and OEM engineers at the time of
vehicle development. This setting must not be changed by
field personnel without the permission of the OEM.


FUNCTION 8

MAX FIELD CURRENT

( Push 8 )

This function allows for the adjustment of the maximum

field current in order to obtain the maximum torque of the

motor.

Min Max Set

Resolution Per Unit Value

0

40

51 to 255 0.185

MAX I

F

= (VAL-51) X 0.185


Important Note: This function is used to optimize motor
and control performance, and this setting will be
determined by GE and OEM engineers at the time of
vehicle development. This setting must not be changed by
field personnel without the permission of the OEM.



FUNCTION 9

REGEN BRAKING C/L

(Push

9)


This function allows for the adjustment of the Regen

braking current limit. High current correlates to shorter

stopping distance.

Resolution

Example

Min

Max Set

Per unit value If set at 20

52A

468A 0 to 255

1.63 amps

84.6 amps


REGEN BRAKE I

A

= (VAL X 1.63) + 52


FUNCTION 10

FIELD CURRENT FOR REGEN

( Push 10 )

This function allows for the adjustment of the field current

to be used during the regen braking mode.

Resolution

Example

Min

Max Set

Per unit value If set at 71

0

40

51 to 255

0.185 amps

3.7 amps


I

F

= (VAL-51) X 0.185


Important Note: This function is used to optimize motor
and control performance and this setting will be
determined by GE and OEM engineers at the time of
vehicle development. This setting must not be changed by
field personnel without the permission of the OEM.

FUNCTION 11

TURN SPEED LIMIT

(Push

11)

This function allows for the adjustment of the speed limit

(maximum battery volts to the motor) when the SL1 signal is

calculated from the turn angle potentiometer by the control

card.

Range

100% to 0% battery volts

Set

51 to 180

Resolution

0.78% per set unit

Example

Setting of 71 = 84.4% of battery volts

Note: To disable speed limit, and assure no 1A hold off, set

this function to a value of zero.


FUNCTION 12

MAX ARMATURE PERCENT ON

( Push 12 )


Same as function 11, this function allows for the

adjustment of the motor speed limit (maximum battery volts

to the motor). The dash display mode selection enables the

speed limit as well as setting the level of speed limit.