Installation Instructions

DUCT FITTINGS

Total

Equivalent Quantity Equivalent

Duct Piece Dimensions

Length*

Used

Length

Round,

1 ft.

straight

(per foot
length)

3-1⁄4

″ x 12″

1 ft.

straight

(per foot
length)

90

° elbow

8 ft.

45

° elbow

6 ft.

3-1⁄4

″ x 12″ or

90

° elbow

15 ft.

3-1⁄4

″ x 12″ or

45

° elbow

9 ft.

3-1⁄4

″ x 12″ or

90

° flat elbow

20 ft.

7

″ round to

3-1⁄4

″ x 12″

transition

1 ft.

3-1⁄4

″ x 12″ to 7″ round

transition

5 ft.

7

″ round to

3-1/4

″ x 12″

transition 90

° elbow

5 ft.

3-1⁄4

″ x 12″ to 7″ round

transition 90

° elbow

15 ft.

Round
wall cap
with damper

30 ft.

3-1⁄4

″ x 12″

wall cap with
damper

30 ft.

7

″ Round

roof cap

30 ft.

Round
roof vent

24 ft.

Use this chart to compute maximum
permissable lengths for duct runs to
outdoors.

Note:

Do not exceed maximum permissable equivalent

lengths!

Maximum duct length:
100 foot for vent hoods.

Flexible ducting:
If flexible metal ducting is used,
all the equivalent feet values in
the table should be doubled.
The flexible metal duct should
be straight and smooth and
extended as much as possible.

Do NOT use flexible plastic ducting.

Total Duct Run

Note:

Any home ventilation system, such as a

ventilation hood, may interrupt the proper flow of
combustion air and exhaust required by fireplaces,
gas furnaces, gas water heaters and other naturally
vented systems. To minimize the chance of interruption
of such naturally vented systems, follow the heating
equipment manufacturer’s guidelines and safety
standards such as those published by NFPA and ASHRAE.

*Actual length of straight duct plus duct fitting equivalent.

Equivalent length of duct pieces are based on actual
tests conducted by GE Evaluation Engineering and
reflect requirements for good venting performance
with any ventilation hood.

This Hood Must Use 7

Round

Duct. It Can Transition To

3-1/4

x 12 Duct

Using a smaller diameter duct size

will reduce performance

Kit - JXDW1

Order kit JXDW1 if your installation

requires horizontal ducting from the

top of the hood through the back

wall and:

• You have an 8 ft. ceiling and need to

use a JXCH Series Chimney Cover, or

• You have a 12

″ cabinet or 12″ soffit

that the hood is to be mounted

beneath.

This kit provides a duct transition

from 7

″ round to

3

1

4

″ x 10″ rectangular for

through-the-wall venting.