HARDWARE

28

CIO Remote CAN Digital I/O Module

GEK-106465A

INTERNAL STATE

V 52/a

V 52/b

SUPERVISION

52 open

ON

ON

OK

52 closed

ON

OFF

OK

TRIP

OFF

OFF

Ok if t < 0.5 s

TRIP with 52 open

OFF

ON

OK

Status of Involved Elements

Inputs to F650

Decision

CIRCUIT

STATUS

OUTPUT

STATUS

(F35-F36)

BREAKER

STATUS

OPERAND

CONTACT

INPUT_00_10

(Va_COIL2)

V 52/a (15-16)

OPERAND

CONTACT

INPUT_00_11

(Vb_COIL2)

V 52/b (17-18)

OPERAND

CONTACT

INPUT_00_15

(SUP_COIL2)

Healthy Open

52

closed

ON

OFF

ON

Healthy Open

52

open

ON

ON

ON

Healthy Closed

52

closed

OFF

OFF

ON (if t < 500 ms)

OFF (if t > 500 ms)

Healthy Closed

52

open

OFF

ON

ON (if t < 500 ms)

OFF (if t > 500 ms)

Defective

Open

52 closed

OFF

OFF

OFF (500 ms delay)

Defective

Open

52 open

OFF

OFF

OFF (500 ms delay)

Defective

Closed

52 closed

OFF

OFF

OFF (500 ms delay)

Defective

Closed

52 open

OFF

OFF

OFF (500 ms delay)

There is a possibility to monitor the trip circuit continuity not only via its auxiliary contact 52/a, but also with auxiliary
contact 52/b. This avoids the need to install a resistance in parallel with auxiliary 52/a. The correct connection is
shown on FIGURE 3-12.

The circuit works in a similar way to the one described in the previous section, but it uses both supervision inputs 15-
16 and 17-18.

The advantage in this case is that circuit supervision with 52 open is more complete, as input V 52/b is used through
contact 52/b, (that is closed when the breaker is open).

We must point out that in this scheme, the tripping contact, shown in the example as the CIO trip relay, can be the
one in the relay (terminals 35 and 36), or be provided by another protection or by the parallel of several protections.
This provides high flexibility in the use of this circuit.

The battery voltage can also be monitored, by using one of the standard digital inputs.