I/O MODULES DESCRIPTION

32

CIO Remote CAN Digital I/O Module

GEK-106465A

5.2. CONTROL

SETTINGS FOR INPUTS/OUTPUTS

This section explains the settings related to CIO inputs/outputs. Modification of these values is performed using the
master unit communication software, EnerVista F650Setup for F650, or GE-CONF for F600.

5.2.1.

INPUT/OUTPUT BOARDS SETTINGS

Settings relative to I/O boards are described in table 5-1:

TABLE 5-1 I/O BOARD SETTINGS

SETTING

HMI

DEFAULT

RANGE

STEP

16 INP + 8OUT

8 INP + 8OUT +

SUPV

I/O board type (available only for

CIO modules)

I/O Board_X Type

NONE

NONE

N/A

Input activation voltage threshold
Group A

Voltage Threshold A_X

80

0 – 255 V

1 V

Input activation voltage threshold
Group B

Voltage Threshold B_X

80

0 – 255 V

1 V

Debounce time Group A

Debounce Time A_X

15

1 – 50 ms

1 ms

Debounce time Group B

Debounce Time B_X

15

1 – 50 ms

1 ms

POSITIVE-EDGE

NEGATIVE-EDGE

POSITIVE

Input type

Input Type_X_CCY POSITIVE

NEGATIVE

N/A

Input signal time delay

Delay Input
Time_X_CCY

0

0 – 60000 ms

1 ms

Output logic type

Output Logic_X_0Z POSITIVE

POSITIVE-

NEGATIVE

N/A

NORMAL

PULSE

Output type

Output Type_X_0Z NORMAL

LATCH

N/A

Output pulse length

Pulse Output
Time_X_0Z

0

0 – 60000 ms

1 ms

Being:

X

I/O board name, depending on the CIO model.

For the I/O board selection in the relay model, associated digits to each board type are as follows:

ASSOCIATED DIGIT

F650PC BOARD

SETTINGS

BOARD TYPE

0 NONE

None

1

16 INP+ 8OUT

Mixed

2

8 INP +8 OUT +SUPV

Supervision