Electrical Requirements
QUIETQUBE® ICE MACHINE HEAD SECTION
CVD® CONDENSING UNIT
CONNECT POWER SUPPLY WIRING DIRECTLY TO L1 & L2 ON THE CONTACTOR.
TORQUE SCREWS TO THE TORQUE VALUE SPECIFICATION ON THE CONTACTOR LABEL.
FOLLOW ALL LOCAL, STATE AND NATIONAL ELECTRICAL CODES.
Ice Machine
Voltage
Phase
Cycle
Maximum Fuse/
Circuit Breaker
Total Amps
QDUALC
115/1/60
208-230/1/60
230/1/50
15 amp
15 amp
15 amp
1.1
0.6
0.6
Important
The QuietQube® Ice Machine Head Section and
CVD Condensing Unit are wired independently from
each other.
Condensing Unit
Voltage Phase
Cycle
Maximum Fuse/
Circuit Breaker
Minimum Circuit
Amps
Minimum Wire Size To
Condensing Unit
CVD1875
208-230/1/60
40
24.3
8 AWG
208-230/3/60
30
16.1
8 AWG
230/1/50
40
23.2
8 AWG
CVD2075
208-230/1/60
50
27.1
8 AWG
208-230/3/60
40
19.9
8 AWG
230/1/50
50
29.9
8 AWG