7 electrical requirements – Manitowoc Ice Q User Manual

Page 17

Advertising
background image

Section 2

Installation Instructions

Part Number 000001530

2-7

Electrical Requirements

QUIETQUBE® ICE MACHINE HEAD SECTION

CVD® CONDENSING UNIT

CONNECT POWER SUPPLY WIRING DIRECTLY TO L1 & L2 ON THE CONTACTOR.

TORQUE SCREWS TO THE TORQUE VALUE SPECIFICATION ON THE CONTACTOR LABEL.

FOLLOW ALL LOCAL, STATE AND NATIONAL ELECTRICAL CODES.

Ice Machine

Voltage

Phase

Cycle

Maximum Fuse/

Circuit Breaker

Total Amps

QDUALC

115/1/60

208-230/1/60

230/1/50

15 amp

15 amp

15 amp

1.1

0.6

0.6

Important

The QuietQube® Ice Machine Head Section and
CVD Condensing Unit are wired independently from
each other.

Condensing Unit

Voltage Phase

Cycle

Maximum Fuse/

Circuit Breaker

Minimum Circuit

Amps

Minimum Wire Size To

Condensing Unit

CVD1875

208-230/1/60

40

24.3

8 AWG

208-230/3/60

30

16.1

8 AWG

230/1/50

40

23.2

8 AWG

CVD2075

208-230/1/60

50

27.1

8 AWG

208-230/3/60

40

19.9

8 AWG

230/1/50

50

29.9

8 AWG