Installation Instructions

Section 2

2-14

Part Number 000001530

C. SUCTION LINE OIL TRAPS

0 to 20 feet (0 to 6.1 m) Rise: The ice machine head
section has one oil trap built in which allows for a
maximum condenser rise of 20 feet (6.1 m) without
additional traps in the suction line.

21 to 35 feet (6.4 to 10.7 m) Rise: The suction line
requires an additional Oil Trap (“S” type) to be installed.
Install the trap as close as possible to midpoint between
the ice machine head section and CVD condensing unit.
S-Trap Kits are available from Manitowoc (refer to chart).

Manitowoc S-Trap Kit

Service Loop

A service loop in the line set permits easy access to the
ice machine for cleaning and service.

The supplied service loop is an installation
requirement. Excess tubing length must be
sufficient to allow 180° rotation of the ice
machine.

A service loop is not considered an oil trap.

The service loop is not included when calculating
length, rise or drop of the tubing run.

Do not use hard rigid copper for the service loop.

Step 3 Lengthening or Reducing Line Set Lengths

When the line set required shortening or lengthening, do
so before connecting the line set to the ice machine
head section or the CVD condensing unit.

! Caution

Do not form unwanted traps in refrigeration lines.
Never coil excess refrigeration tubing.

Model

S-Trap Kit

Number

Tubing Size

QDUALC

K00164

7/8 inch

(22.2 mm)

21’ OR MORE

RISE

ADDITIONAL

TRAP KIT

REQUIRED

SV1751

SV1760

! Caution

If a line set has a rise followed by a drop, another rise
cannot be made. Likewise, if a line set has a drop
followed by a rise, another drop cannot be made.

! Caution

Do not form unwanted traps in refrigeration lines.
Never coil excess refrigeration tubing.