4-8.

Extension Cord Data

When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.

NOTE

Input Voltage

Input Power

Phase

Hertz

Fuse Size Or

Circuit Breaker Rating

Conductor Size

Max. Cord Length

208 V

3

60

Time-Delay

2

60 A

Normal Operating

3

80 A

8 AWG

89 ft (27 m)

230 V

3

60

Time-Delay

2

60 A

Normal Operating

3

70 A

8 AWG

108 ft (33 m)

460 V

3

60

Time-Delay

2

30 A

Normal Operating

3

35 A

10 AWG

284 ft (87 m)

575 V

3

60

Time-Delay

2

20 A

Normal Operating

3

30 A

12 AWG

268 ft (82 m)

400 V

3

50

Time-Delay

2

25 A

Normal Operating

3

35 A

12 AWG

155 ft (47 m)

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose − no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).