SECTION 4—INSTALLATION

Supine Bath Tub

22

Part No 1096926

Plumbing Hook-Up

ƽ WARNING

Be certain ALL plumbing work is performed by a qualified plumber and is in

compliance with local codes.

NOTE: For this procedure, refer to Refer to FIGURE 4.5.

NOTE: For installation details refer to Plumbing Installation on page 23.

CAUTION

The 2 inch PVC stub MUST be recessed into the floor to make the elbow flush with the

floor. For Model IH6300ADH, this will allow smooth up and down movement of the

hose. Otherwise, drain tubing and fittings could be crushed at low point of

operation.

1. Install the plumbing hook‐ups per FIGURE 4.5.

FIGURE 4.5 Plumbing Hook-Up

10.0 in

(254 mm)

Cold

Hot

3.5 in

(89 mm)

5.5 in

(140 mm)

6.5 in

(165 mm)

3/4 in. Ball Valve

DETAIL “B” - DRAIN AND ROUGH-IN LOCATIONS

Drain

Elbow

Front of Tub

DETAIL “A” - HOOK UP LOCATIONS

MUST be a

minimum of 6 in

above the floor

6 in.

(152 mm)

Tub

Centerline of Tub

Back of Tub

36 in.

(915 mm)

Wall

Drain

2 in. PVC stub

Advertising