GEM0650/0956/1256 Remote

Operation: Refrigeration

Page

22

Low Condensing Temperature
The refrigeration system under low condenser air temperatures is much the same as it is under higher
temperatures, with the exception that the resulting low head pressures cause the head pressure control to
close off the liquid line between the condenser and the receiver.

This forces more refrigerant into the condenser (with a small amount of discharge gas going into the receiver to
maintain pressure until the head pressure is built back up to 180 PSIG). At that pressure the valve opens up
the liquid line from the condenser to the receiver.

Refrigeration Schematic

Remote Condenser

Discharge
Line

Liquid Line

Detail of Head Pressure Control Valve

Head Pressure
Control Valve

Receiver

Compressor

Evaporator

Suction Line

Thermostatic Expansion Valve

Liquid Line Valve