Chapter 2 Installation

Series 780S Instruction Manual

2-2

IM-78S-B

Unobstructed Flow Requirements

Select an installation site that will minimize possible distortion in the
flow profile. Valves, elbows, control valves and other piping compo-
nents may cause flow disturbances. Check your specific piping condi-
tion against the examples shown below. To achieve accurate and re-
peatable performance, install the flow meter using the recommended
number of straight run pipe diameters upstream of the sensor.

Piping Condition

Upstream

(1)

Requirements

Single 90° elbow or T-piece

1 D

Reduction (4:1)

3 D

Expansion

3 D

After a control valve

3 D

Two 90° elbows (in same plane)

3 D

Two 90° elbows (different planes)

5 D

(1) Number of diameters (D) of straight pipe required between upstream disturbance and the flow meter sensor.

Table 2-1. Pipe Length Requirements for Installation

Installing the Flow Meter

SIERRA

Flow direction indicator
should point downstream
in the direction of flow

FLOW

Enclosure

adjustable to any

viewing position

Figure 2-1. Flow Meter Orientation (Flange Connection Shown)

When positioning the flow meter, refer to the flow direction indicator
attached to the probe. For proper operation, install the meter with the
flow direction indicator pointing downstream in the direction of flow.
Installing the meter opposite this direction may result in inaccurate
flow measurement.