Chapter 3 Operation

Series 780S Instruction Manual

3-8

IM-78S-B

Time Response Delay Adjustment

Changing the Time Response Delay using the LCD Display
1. Select FUNCTION, enter the password. Select FUNCTION

again until Time Response appears on the display.


2. Use UP or DOWN to adjust the time response delay from 0.10

to 7.2 seconds.


3. Select FUNCTION again to advance to the next option, or after

12 seconds of non-activity the meter returns to the Run Mode
and the new time response setting is in effect.

Changing the Time Response Delay using the Single-Digit LED
1. Set the DVM to voltage mode and connect between Vout+ and

Vout– on the flow meter terminal block. Select the desired
range. Press the FUNCTION button until a solid “9” appears on
the LED.


2. Adjust the UP or DOWN button until the DVM indicates the de-

sired voltage (as shown in the following table).


Volts

Indicated

on DVM

Time

Response
(Seconds)

Volts

Indicated

on DVM

Time

Response
(Seconds)

Volts

Indicated

on DVM

Time

Response
(Seconds)

Volts

Indicated

on DVM

Time

Response

(Seconds)

0.5

0.1

1.0

0.3

1.5

0.5

2.0

0.7

2.5

1.2

3.0

1.8

3.5

2.4

4.0

3.6

4.5

4.8

5.0

7.2


3. Press FUNCTION to advance to the next option, or after 12

seconds of non-activity the meter returns to the Run Mode and
the new time response delay setting is in effect.