Chapter 2 Installation

Series 780S Instruction Manual

2-6

IM-78S-B

DC Power Wiring
The DC power wire size must be 26 to 16 AWG with the wire
stripped 1/4 inch (6 mm). Connect 18 to 30 VDC (625 mA load,
maximum) to the terminals marked PWR+ and PWR– on the terminal
block. Torque all connections to 4.43 to 5.31 in-lbs (0.5 to 0.6 Nm).

All EEx installations must use an approved EEx fitting at both cable
entries into the enclosure. If conduit seals are used, they must be in-
stalled within 18 inches of the enclosure.

1

2

15

16

DC Power (+)

DC Power (–)

NEMA 4X Enclosures

Figure 2-6. DC Input Power Connections

DC Power (+)

DC Power (–)

1
2
3
4
5
6
7
8
9

10

20
19
18
17
16
15
14
13
12
11

Hazardous-Area Enclosures

Figure 2-7. DC Input Power Connections

Warning!

All wiring procedures

must be performed with

the power Off.