Installation instructions – Sanyo CL2462R User Manual

Page 23

Advertising
background image

– 23 –

SM830092

8. INSTALLATION INSTRUCTIONS

Table 3

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

Model

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

(ft.)

(ft.)

(ft.)

(oz./ft.)*

C2462R, CL2462R

23

132

50

0.43

* If total tubing length becomes 23 to 132 ft. (max.), additional refrigerant (R410A) charge of 0.43 oz./ft. is required.

No additional charge of compressor oil is necessary.

1)

Tubing Length

• Refrigerant tubing between the indoor and

outdoor units should be kept as short as
possible.

• Select and decide the installation location

so that the length of the refrigerant tubing
will be within the limits given in Table 1.

Fig. 1

Tubing length (L)

INDOOR
UNIT

OUTDOOR
UNIT

Elevation difference (H)

0711_M_I