12. SERVICE PROCEDURES

(2)

A Sensor is Defective.

1

Indoor (heat exchanger) coil temp. Sensor is defective.

(a) Open (=No continuity in sensor)

Compressor and outdoor fan repeat ON for 10 minutes and OFF for 6 minutes
when sensor opens.

(b) Short

“Freeze Prevention” does not operate when dehumidified water is frozen on the
indoor coil.

2

Room temp. Sensor (in the remote control unit) is defective.

(a) Open (=No continuity in sensor)

Neither outdoor fan nor compressor runs.

(b) Short

Outdoor fan and compressor do not stop. — Excessive cooling.