12. SERVICE PROCEDURES

(3)

Checking the Electrical Components

1)

Measurement of Insulation
Resistance

• The electrical insulation is acceptable

when the resistance exceeds 2 M

.

1

Power Supply Wires

Clamp the earthed wire of the Power
Supply wires with a lead clip of the
insulation resistance tester and mea-
sure the resistance by placing a probe
on either of the power wires. (Fig. 16)

Then measure the resistance between
the earthed wire and the other power
wires. (Fig. 16)

2

Indoor Unit

Clamp an aluminum plate fin or copper
tube with the lead clip of the insulation
resistance tester and measure the
resistance by placing a probe on the
terminal plate (Fig. 17)

3

Outdoor Unit

Measure the resistance by placing a
probe on the terminal plate in the same
manner as explained above 2 . (Fig. 17)

4

Measurement of Insulation Re-
sistance for Electrical parts

• Disconnect the connector of the

desired electric part from terminal
plate, P.C.B. Ass’y, etc. (Fig. 18)

• Similarly, disconnect the lead wires from

compressor, capacitor, etc. (Fig. 19)

• Measure the resistance in the same

manner as illustrated on the right.

Refer to Electrical Wiring Diagram.

If the probe does not enter the hole
because the hole is too narrow, use a
probe with a thinner pin.

Earthed wire

Clip

Probe

Insulation
tester

0638_X_S

Fig. 16

Copper
tube or
metallic part

Clip

Insulation
tester

Probe

Terminal plate

0639_X_S

Fig. 17

Copper
tube or
metallic part

Clip

Insulation
tester

Probe

0640_X_S

Fig. 18

From fan motor,
compressor and other
parts.

Clip

Probe

Insulation
tester

Metallic
part

0641_X_S

Fig. 19

NOTE