Installation instructions – Sanyo CL2462R User Manual

Page 26

Advertising
background image

– 26 –

SM830092

8. INSTALLATION INSTRUCTIONS

Wind Shield for "CL" Model

It is recommended to use wind shields for "CL" model

(Fig. 5b). "CL" model is designed to use in low outdoor

temperature conditions.

General

When the outdoor unit is installed in a position exposed

to strong wind (like seasonal winds with low air tempera-

ture in winter), a suitable wind shield must be installed

on the outdoor unit.

This unit is designed so that the fan of the outdoor unit

runs at low speed when the air conditioner is operated at

low outdoor air temperatures. When the outdoor unit is

exposed to strong wind, the system pressure drops

because of the freeze protector.

For outer dimensions of the wind shield, see Fig. 5c.

IMPORTANT

Wind shield
(air discharge side)

Front

3 -

ø1-9/16"

hole

6 -

ø15/64" hole

9-27/32"

21-5/8"

15/16"

5-3/16"

22-7/16"

1/2"

23-15/32"

21-13/16"

5-5/32"

9-27/32"

9-27/32"

1-1/16"

21-13/16"

Fig. 5b

Fig. 5c

CL2462R

Recommended outer dimensions of wind shield
(field supply)