(4) Outdoor Fan Speed Control

(1) C2462R Type

In low outdoor temperature, the outdoor fan is set automatically from HIGH to LOW
to prevent the indoor heat exchanger from freezing.

When the outdoor temperature falls below 78

°

F, the outdoor fan is set from HIGH to

LOW automatically. When the outdoor temperature rises to 82

°

F, the outdoor fan is

set from LOW to HIGH automatically.

(2) CL2462R Type

In low outdoor temperature, the outdoor fan is set automatically from HIGH to MED,
LOW to prevent the indoor heat exchanger from freezing.

When the outdoor temperature falls below 77

°

F, the outdoor fan is set from HIGH to

MED automatically. When the outdoor temperature rises to 81

°

F, the outdoor fan is

set from MED to HIGH automatically.

When the outdoor temperature falls below 59

°

F, the outdoor fan is set from MED to

LOW automatically. When the outdoor temperature rises to 63

°

F, the outdoor fan is

set from LOW to MED automatically.

When the outdoor temperature falls below 50

°

F, the hot gas bypass valve opens

and keeps the pressures up by allowing some hot gas to be bypassed to the suction
of the compressor.

11. PROCESSES AND FUNCTIONS

Fig. 14

OFF

ON

L

M

H

760

380

230

FAN ROTATION RPM

HGBV

(HOT GAS

BYPASS VALVE)

47

(8.3)

50

(10)

59

(15)

63

(17)

77

(25)

81

(27)

OUTDOOR AIR TEMPERATURE

°

F DB

2217_X_S