Sanyo ECO R410A User Manual

Page 31

Advertising
background image

31

CAUTION

Insulate both gas and liquid

tubes.

To insulate tubes

(1) Wrap the flare nuts with the supplied white insulating tape.

(2) Wrap the flare nuts with the supplied flare insulator.

(3) Fill the clearance between the union insulator and flare insulator

with black insulating tape. Fasten both ends of the flare insulator

with the supplied vinyl clamps.

3-29. Installing the Drain Piping

(1) When rear-side drain piping is required bend the drain hose

attached to the indoor unit by 90° . Connect a drain pipe (field
supply) to the drain hose through the rear tubing outlet in the
rear panel. Use a hard PVC pipe (VP20) for the drain piping.

(2) Ensure that the drain pipe has a downward gradient of 1/100 or

more and that there are no water traps.

(3) Provide insulation for the drain pipe.

(4) After the drain piping is completed, pour water into the drain pan

to check that the water drains smoothly.

(5) Remove any dust or debris in the drain pan so that the pipe is

not clogged.

3-30. Installing the Remote Controller

A remote controller (optional wired remote controller) can
be mounted in the indoor unit (floor-standing type).

(1) Remove the cover of the optional wired remote controller.

(Fig. 3-68)

(2) Remove the front panel. Remove the screws and fixture.

(Fig. 3-69)

(3) Place the remote controller into the space in the unit as shown in

Fig. 3-69. Assemble the lead wires of the remote controller to its
rear side center and route them to the lead wire guide.

(4) Secure the fixture using the supplied screws.

To remove the cover from the remote controller, insert a
screwdriver between the cover and the controller as shown
in the figure above, and pry off the cover.

CAUTION

Water leaks may occur if the drain

pipes are connected inadequately.

Fig. 3-68

Insulating tape (black)

Insulating tape (white)

Flare insulator

Insulator

Flare nut

Vinyl clamps

Insulating tape

Fig. 3-65

Fig. 3-66

Drain hose

Drain pipe (PVC)

Fig. 3-67

Drain hose (supplied)

Drain insulator (supplied)

Vinyl clamp
(supplied)

Hose band
(supplied)

Hard PVC pipe VP20

(field supply)

Insulating tape
(supplied)

Vinyl clamps
(supplied)

Drain hose insulator
(field supply)

Fig. 3-69

controller

Remote

Lead wire guide

Screw

Fixture