Sanyo ECO R410A User Manual

Page 42

Advertising
background image

42

Fig. 5-10

Fig. 5-11

5-4. Taping the Tubes

(1) At this time, the refrigerant tubes (and electrical wir-

ing if local codes permit) should be taped together

with armoring tape in 1 bundle. To prevent the con-

densation from overflowing the drain pan, keep the

drain hose separate from the refrigerant tubing.

(2) Wrap the armoring tape from the bottom of the out-

door unit to the top of the tubing where it enters the

wall. As you wrap the tubing, overlap half of each

previous tape turn.

(3) Clamp the tubing bundle to the wall, using 1 clamp

approx. each ft. (Fig. 5-10)

NOTE

Do not wind the armoring tape too tightly since this will

decrease the heat insulation effect. Also ensure that the

condensation drain hose splits away from the bundle

and drips clear of the unit and the tubing.

5-5. Finishing the Installation

After finishing insulating and taping over the tubing, use

sealing putty to seal off the hole in the wall to prevent

rain and draft from entering. (Fig. 5-11)

Insulated tubes Drain hose

Clamp

Tubing

Apply putty here