Electrical wiring – Sanyo ECO R410A User Manual

Page 33

Advertising
background image

33

4. ELECTRICAL WIRING

4-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unit

as shown on its nameplate, then carry out the wiring

closely following the wiring diagram.

(2) Provide a power outlet to be used exclusively for

each unit, and a power supply disconnect and circuit

breaker for overcurrent protection should be provid-

ed in the exclusive line.

(3) To prevent possible hazards from insulation failure,

the unit must be grounded.

(4) Each wiring connection must be done in accordance

with the wiring system diagram. Wrong wiring may

cause the unit to disorder or become damaged.

(5) Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can be

very dangerous. The manufacturer will accept no

responsibility for any damage or malfunction that

occurs as a result of such unauthorized changes.

(7) Regulations on wire diameters differ from locality

to locality. For field wiring rules, please refer to your

LOCAL ELECTRICAL CODES before beginning.

You must ensure that installation complies with all

relevant rules and regulations.

(8) To prevent malfunction of the air conditioner caused

by electrical noise, care must be taken when wiring

as follows:

The remote control wiring and the inter-unit control

wiring should be wired apart from the inter-unit power

wiring.

(9) If the power supply cord of this appliance is dam-

aged, it must be replaced by a repair shop appoint-

ed by the manufacture, because special purpose

tools are required.

4-2. Recommended Wire Length and Wire Diameter for Power Supply System

Indoor unit

Time delay fuse or

circuit capacity

K

U, UM

Type

10 – 16A
10 – 16A
10 – 16A

F, FM

Control wiring

(A) Inter-unit (between outdoor and

indoor units) control wiring*

(B) Remote control wiring

(C) Control wiring for group control

(D) Inter-outdoor unit control wiring

AWG #18 (0.75 mm

2

)

Max. 3,280 ft.

Max. 1,640 ft.

Max. 650 ft. (Total)

Max. 980 ft.

AWG #18 (0.75 mm

2

)

AWG #18 (0.75 mm

2

)

AWG #18 (0.75 mm

2

)

NOTE

* With ring-type wire terminal.