Indoor Unit

KHS1872

Outdoor Unit CH1872

• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.

Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in

heating mode. (Refer to "8-2. Overload prevention during heating.")

NOTE

Indoor discharge air temperature °F(°C)

23

(–5)

32

(0)

41

(5)

50

(10)

59

(15)

68

(20)

77

(25)

Outdoor inlet air D.B. temp. °F(°C)

70°F (

21°C)

63°F (

17°C

)

Indoor air temp

.73°F (23°C

)

Outdoor inlet air D.B. temp. °F(°C)

23

(–5)

32

(0)

41

(5)

11

10

9

8

7

6

5

50

(10)

59

(15)

68

(20)

77

(25)

Operating current (A)

63°F (

17°C)

Indoor air temp.73

°F (23°C

)

70°F (

21°C)

23

(–5)

32

(0)

41

(5)

50

(10)

131(55)

122(50)

113(45)

104(40)

95(35)

86(30)

59

(15)

68

(20)

77

(25)

Outdoor inlet air D.B. temp. °F(°C)

70°F (

21°C)

63°F (

17°C)

Indoor air temp.73

°F (23°C)

High pressure at wide tube service valve

psig (MPaG

)

494

(3.4)

421

(2.9)

348

(2.4)

275

(1.9)

Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)

(1) High pressure performance chart

(2) Operating current performance chart

(3) Indoor discharge air performance chart