2. protective functions, Overload prevention during heating, Freeze prevention – Sanyo KHS2472 User Manual

Page 40

Advertising
background image

Overload prevention during heating

During HEAT operation, the temperature of the indoor heat

exchanger is used to control the frequency and lessen the load

on the compressor before the protective device is activated.

Cold-air prevention during heating

Compressor discharge temperature control

During heating, the fan speed is set to "LL" (very low) or stopped.

As the temperature of the indoor heat exchanger rises, the fan

speed is changed to the set speed.

Freeze prevention

During COOL or DRY operation, freezing is detected and

operation is stopped when the temperature of the indoor heat

exchanger matches the conditions below.

1. Freeze-prevention operation is engaged when the

temperature of the indoor heat exchanger is below 43°F(6°C).

2. Restart after freeze-prevention operation occurs when the

temperature of the indoor heat exchanger reaches 46°F(8°C)

or above.

a.

Area: Automatic capacity control

b.

When Point A has been exceeded, the operation frequency is

reduced by a certain proportion.

c.

Area: Frequency increase is prohibited.

d.

At Point B and below, overload prevention is ended and

control is the same as in the

a

area.

a.

Area: Automatic capacity control

b.

When the temperature drops below Point A, the operation

frequency is reduced by a certain proportion.

c.

Area: Frequency increase is prohibited.

d.

When the temperature reaches Point C or above, freezing

prevention is ended and control is the same as in the

a

area.

*

When the temperature drops to below 36°F(2°C)

(continuously for 2 minutes or longer), the compressor stops.

Once the freeze condition is detected, the air conditioner will

work less than the maximum frequency until it is turned off.

Approx.

127

(53)

At stability of operation

At start of operation

A

High

LL

Stopped

A

*

B

C

B

Indoor heat exchanger

A. Control start

B. Control end

Set fan speed

77

(25)

86

(30)

Approx. 104

(40)

a

b

c

d

a

b

c

d

Indoor heat exchanger

temperature °F(°C)

Indoor heat exchanger

temperature

°F

(

°C

)

Indoor heat exchanger

temperature °F(°C)

Approx.

117

(47)

36

(2)

43

(6)

46

(8)

The fan speed is forcibly changed to "LL" beginning 30 seconds

after the thermostat turns OFF.

At stability of operation refers to operation when the room

temperature has approached the set temperature.

When HEAT operation starts, the indoor fan is stopped until the

temperature of the indoor heat exchanger reaches 68°F(20°C)

or higher, or until the room temperature reaches 59°F(15°C) or

higher.

This function controls the operation frequency to prevent the

compressor discharge temperature from rising more than a

specified temperature.

a.

Area: Automatic capacity control.

b.

When the temperature rises above Point A, the operation

frequency is reduced at a specified rate.

c.

Area: Further frequency increase is prohibited.

d.

When the temperature falls below Point B, prevention of a rise

in frequency is released and the air conditioner operates as in

a

area.

*

The compressor will stop if the temperature of the compressor

discharge exceeds 248°F(120°C) due to shortage of gas or

other reason.

Approx.

214

(101)

A

B

a

b

c

d

Compressor discharge temperature

°F

(

°C

)

Approx.

201

(94)

NOTE

8-2. Protective Functions

40

Advertising
This manual is related to the following products: