Ct (peak current cut-off control), Defrost detection and release, Defrosting sequence – Sanyo KHS2472 User Manual

Page 41

Advertising
background image

This function prevents the circuit breaker or fuse from operating

to open the circuit. This function works when electrical current

has increased due to an increase in the cooling / heating load,

or to a decrease in the power supply voltage. In these cases,

operation frequency is reduced or operation is interrupted auto-

matically to control the electrical current for operation.

When the cause of the increase in electrical current is rectified,

the system will resume operation in the original mode.

Electrical current setting for COOL operation is

used during DEFROST operation.

Cooling Dry Heating

Peak current cut-off trips

22.5

Hz down

14.0

15.0

(A)

CT (Peak current cut-off control)

NOTE

NOTE

Heating operation

Frost sensing

Reverse-cycle defrosting operation

Defrosting Sequence

Releasing of defrosting

Outdoor fan ON

4-way valve ON

Outdoor heating exchanger temp. is over 57.2°F (14°C).

Defrosting operation lasts 12 minutes (maximum).

2 minutes after it is stopped, compressor is ON.

4-way valve is ON. Outdoor fan is ON.

If the air conditioner is turned off during the defrosting

cycle, it will continue defrosting and turn itself off after

defrosting is completed.

Compressor 1 minute after it is stopped,

compressor is ON.

Outdoor fan OFF

Indoor fan OFF

4-way valve OFF

Operation lamp

Reverse-Cycle Defrosting

Defrost detection and release

Repeatedly switches between red

and orange illumination.

Defrost detection occurs in either of the following cases:

The temperature of the heat exchanger remains at

or below the L2 line for 120 minutes after the start

of HEAT operation.

Outdoor heat

exchanger temp.

Ambient temp.

0

L1

L2

Frosting area

The temperature of the heat exchanger remains at

or below the L1 line for 3 minutes after the start of

HEAT operation.

<

KHS1872

>

Cooling Dry Heating

Peak current cut-off trips

22.5

Hz down

14.0

17.5

(A)

<

KHS2472

>

41