1-5. Additional Materials Required for Installation

1.

Refrigeration (armored) tape

2.

Insulated staples or clamps for connecting wire

(See local codes)

3.

Putty

4.

Refrigeration lubricant

5.

Clamps or saddles to secure refrigerant tubing

2. Installation Site Selection

2-1. Indoor Unit

AVOID:

direct sunlight.

nearby heat sources that may affect performance of the unit.

areas where leakage of flammable gas may be expected.

places where large amounts of oil mist exist.

DO:

select an appropriate position from which every corner of

the room can be uniformly cooled. (High on a wall is best.)

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have the

shortest run to the outside. (Fig. 1)

allow room for operation and maintenance as well as unre-

stricted air flow around the unit. (Fig. 2)

install the unit within the maximum elevation difference (H)

above or below the outdoor unit and within a total tubing length

(L) from the outdoor unit as detailed in Table 3 and Fig. 3a.

Install the indoor unit more than 3.3' (1 m) away from any

antenna or power lines or connecting wires used for television,

radio, telephone, security system, or intercom. Electrical noise

from any of these sources may affect operation.

Drain hose

Indoor unit

Outside drainage

Fig. 1

2" (5 cm)

min.

6" (15 cm)
min.

Front View

2" (5 cm)

min.

Fig. 2

INDOOR
UNIT

Tubing length (L)

OUTDOOR
UNIT

Elevation
difference (H)

Fig. 3a

WARNING

To prevent abnormal heat genera-

tion and the possibility of fire, do

not place obstacles, enclosures

and grilles in front of or surround-

ing the air conditioner in a way

that may block air flow.

* If total tubing length becomes 25 to 98 ft. (Max.) or 33 to 98 ft. (Max.), charge additional refrigerant (R410A) by 0.27 oz./ft.

No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.

Indoor unit

Floor level

Wall

Minimum height
from floor level

5' (1.5 m)

Fig. 3b

For stable operation of the

air conditioner, do not

install wall-mounted type

indoor units less than 5'

(1.5 m) from floor level.

CAUTION

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

Model

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

(ft.)

(ft.)

(ft.)

(oz./ft.)*

KHS1872

25

98

49

0.27

KHS2472

33

98

49

0.27

Table 3